GE Industrial Solutions ASTAT BP User Manual

Page 23

Advertising
background image

ASTAT BP User Manual

23

GE Industrial Solutions

©2013 GE Company All Rights Reserved

44..77

Overview of All Mode Pages and Factory Defaults

Appears only in

Maximized

9

Display Page

Main Settings

- ****

-

Start Settings

- **** -

Stop Settings

- **** -

DUAL Settings

Parameters

Function & Default

Function & Default

Function & Default

Function & Default

Function & Default

Motor Current

0

Language

English

Soft Start Curve

0(Standard)

Soft Stop Curve

0(Standard)

Starting VOLT-2

30%

Line Voltage

0 Volt

Starter Current

58 AMP.

Kickstart Time

0 SEC.

Ramp DOWN Time

0 SEC.

Starting CURR-2

100%

Option PCB

Not Installed

Motor Current

58 AMP.

Starting Voltage

30 %

End Torque

0 (MIN.)

Current Limit-2

350% of Im

POWER

0

RATED POWER

30KW

Starting Current

100 %

Store Settings

Stop Settings

Ramp UP-2

10 SEC.

POWER FACTOR

0

LINE/DELTA Conf.

Line

Current Limit

350% OF Im

Ramp DOWN-2

0 SEC.

Line Voltage

400 Volt

Ramp UP Time

10 SEC.

Motor Current-2

31 Amp.

Undercurrent FLT

0% of Im

Max. Start Time

30 SEC.

Store Settings

Dual Settings

Undercurrent DLY

10 SEC.

Number of Starts

10

O/C JAM Fault

200% OF Im

Duty Cycle Time

30 Min.

O/C JAM Delay

0.5 Sec.

Start Lockout

15 Min.

Overload Class

IEC CLASS 10

Store Settings

Start Settings

Overload Protect

Enabled

Undervoltage FLT

75%

Undervoltage DLY

5 SEC.

Overvoltage FLT

120%

Overvoltage DLY

2 SEC.

DISPLAY MODE

MINIMIZED

SETTING LOCK

PARAM NOT LOCKED

Store Settings

Main Settings

9

Refer to section 4.7.2 on page 26 for changing display mode from MINIMIZED MODE to MAXIMIZED MODE.