GE Industrial Solutions ASTAT BP User Manual
Page 23
ASTAT BP User Manual
23
GE Industrial Solutions
©2013 GE Company All Rights Reserved
44..77
Overview of All Mode Pages and Factory Defaults
Appears only in
Maximized
9
Display Page
Main Settings
- ****
-
Start Settings
- **** -
Stop Settings
- **** -
DUAL Settings
Parameters
Function & Default
Function & Default
Function & Default
Function & Default
Function & Default
Motor Current
0
Language
English
Soft Start Curve
0(Standard)
Soft Stop Curve
0(Standard)
Starting VOLT-2
30%
Line Voltage
0 Volt
Starter Current
58 AMP.
Kickstart Time
0 SEC.
Ramp DOWN Time
0 SEC.
Starting CURR-2
100%
Option PCB
Not Installed
Motor Current
58 AMP.
Starting Voltage
30 %
End Torque
0 (MIN.)
Current Limit-2
350% of Im
POWER
0
RATED POWER
30KW
Starting Current
100 %
Store Settings
Stop Settings
Ramp UP-2
10 SEC.
POWER FACTOR
0
LINE/DELTA Conf.
Line
Current Limit
350% OF Im
Ramp DOWN-2
0 SEC.
Line Voltage
400 Volt
Ramp UP Time
10 SEC.
Motor Current-2
31 Amp.
Undercurrent FLT
0% of Im
Max. Start Time
30 SEC.
Store Settings
Dual Settings
Undercurrent DLY
10 SEC.
Number of Starts
10
O/C JAM Fault
200% OF Im
Duty Cycle Time
30 Min.
O/C JAM Delay
0.5 Sec.
Start Lockout
15 Min.
Overload Class
IEC CLASS 10
Store Settings
Start Settings
Overload Protect
Enabled
Undervoltage FLT
75%
Undervoltage DLY
5 SEC.
Overvoltage FLT
120%
Overvoltage DLY
2 SEC.
DISPLAY MODE
MINIMIZED
SETTING LOCK
PARAM NOT LOCKED
Store Settings
Main Settings
9
Refer to section 4.7.2 on page 26 for changing display mode from MINIMIZED MODE to MAXIMIZED MODE.