Function &

Default

Range

Unit

Description

Overvoltage FLT

120%

110-125

% of

mains

voltage

Sets Overvoltage Fault level.

Trips the ASTAT-BP when mains voltage increases above the

level that was set for a time longer than

Overvoltage

DLY. Can not be set lower than the Undervoltage FLT

setting.

Overvoltage DLY

2 SEC.

1 –10

sec.

Sets Overvoltage Fault delay.

17

DISPLAY MODE

MINIMIZED

MINIMIZED;

MAXIMIZED

Sets the displayed mode pages while browsing. There are

two display modes:

MINIMIZED – Display of pre-selected Settings for standard

applications.

MAXIMIZED – Display of all possible Settings.

Setting Display Mode to

MINIMIZED will minimize the LCD

displays. (Refer to section 4.6 on page 22 for more details)

SETTINGS LOCK

PARAM NOT LOCKED

PARAM NOT

LOCKED;

PARAM LOCKED

The software lock prevents undesired parameter

modification.

When locked, upon pressing

Store ,

▼ or▲ keys, the LCD

displays:

Unauthorized Access

Store Settings

Main Settings

Storing modified parameters

18

To store selected parameters scroll through all parameters

until you reach

Store Settings Main Settings, then

press the Set key.

After you store a parameter successfully the

Data Saved

OK message will display.

If ASTAT-BP fails to store the parameter the LCD Will display

the

Storage Error message (refer to section 7 on page

56 for more details).

4.7.3

Start Settings

19

– Page 2

Function &

Default

Range

Unit

Description

Soft Start Curve

0(Standard)

0

(Standard)

1 !!

2 !!

3 !!

4 (Torque)

Sets ASTAT-BP’s Soft Start Curve.

20

Refer to section 4.7.3.1 on page 31.

17

Becomes operational only after the start signal.

18

Pressing the Set key when the Store Settings Xxxxx Settings message does not appear on the display has no effect.

19

Displays in MINIMIZED MODE and MAXIMIZED MODE.

20

When ASTAT-BP is connected in DELTA Conf. only Soft Start Curve 0 (Standard) is applied.