GE Industrial Solutions ASTAT BP User Manual
Page 28
ASTAT BP User Manual
28
GE Industrial Solutions
©2013 GE Company All Rights Reserved
Function &
Default
Range
Unit
Description
Overvoltage FLT
120%
110-125
% of
mains
voltage
Sets Overvoltage Fault level.
Trips the ASTAT-BP when mains voltage increases above the
level that was set for a time longer than
Overvoltage
DLY. Can not be set lower than the Undervoltage FLT
setting.
Overvoltage DLY
2 SEC.
1 –10
sec.
Sets Overvoltage Fault delay.
17
DISPLAY MODE
MINIMIZED
MINIMIZED;
MAXIMIZED
Sets the displayed mode pages while browsing. There are
two display modes:
MINIMIZED – Display of pre-selected Settings for standard
applications.
MAXIMIZED – Display of all possible Settings.
Setting Display Mode to
MINIMIZED will minimize the LCD
displays. (Refer to section 4.6 on page 22 for more details)
SETTINGS LOCK
PARAM NOT LOCKED
PARAM NOT
LOCKED;
PARAM LOCKED
The software lock prevents undesired parameter
modification.
When locked, upon pressing
Store ,
▼ or▲ keys, the LCD
displays:
Unauthorized Access
Store Settings
Main Settings
Storing modified parameters
18
To store selected parameters scroll through all parameters
until you reach
Store Settings Main Settings, then
press the Set key.
After you store a parameter successfully the
Data Saved
OK message will display.
If ASTAT-BP fails to store the parameter the LCD Will display
the
Storage Error message (refer to section 7 on page
56 for more details).
4.7.3
Start Settings
19
– Page 2
Function &
Default
Range
Unit
Description
Soft Start Curve
0(Standard)
0
(Standard)
1 !!
2 !!
3 !!
4 (Torque)
Sets ASTAT-BP’s Soft Start Curve.
20
Refer to section 4.7.3.1 on page 31.
17
Becomes operational only after the start signal.
18
Pressing the Set key when the Store Settings Xxxxx Settings message does not appear on the display has no effect.
19
Displays in MINIMIZED MODE and MAXIMIZED MODE.
20
When ASTAT-BP is connected in DELTA Conf. only Soft Start Curve 0 (Standard) is applied.