GE Industrial Solutions ASTAT BP User Manual
Page 86
ASTAT BP User Manual
86
GE Industrial Solutions
©2013 GE Company All Rights Reserved
Parameter
#
Range
Default
Slow SP & Saving Parameters
Energy Saving
57
0..10
10 ( Max Save)
Slow Speed_TRQ.
58
1..10
8
Max_Slow_SP_Time
59
1..60
30 (Seconds)
Reserved
60..63
Fault Settings
Phase Loss
64
0..1 (0-Disabled, 1-Enabled)
1 (Enabled)
Phase Sequence
65
0..1 (0-Disabled, 1-Enabled)
0 (Disabled)
Auto Reset
66
0 / 1 (0-Disabled, 1-Enabled)
0 (Disabled)
Thermistor Type
67
0 / 1 (0 - PTC, 1 - NTC)
0 (PTC)
Thermistor Trip
68
0..100 Tenth Kohm 0.1..10 K
0 (Disabled)
Undercurrent RST
69
10..120 (&121=Disabled)
121 (Disabled)
Reserved
70-72
I/O Settings
PROG. Input # 7
73
0..2 (0=En.Save,1=S.Spd,2=Rst)
0 (Reset)
PROG. Input # 8
74
0..2 (0=D.Set.,1=Rvrs,2=Rst)
0 (Dual Set)
PROG. Fault Relay
75
0..1 (0=Fault close, 1=Fault open)
0 (Fault close)
Relay ON Delay
76
0..3600
0 (Seconds)
Realy OFF Delay
77
0..3660
0 (Seconds)
Analog Output
78
0- Current, 0..200% of motor_fla
0- Current
Reserved
79..80
COMM. Parameters
COMM. Protocol
81
0-Modbus,1-Profibus, 2-DeviceNet
0-Modbus
Baud Rate
82
12..96 (*100) Auto for Profibus
96 (9600 bps)
Parity Check
83
0/1/2 (Even / Odd / No)
0 (Even)
Station Number
84
1..247 & (248= Off)
248 (Off)
1..126 & (127= Off) for Profibus
S. Link Par. Set
85
0 (Disable), 1 (Enable)
0 (Disable)
S. Link Control
86
0 (Disable), 1 (Enable)
0 (Disable)
Reserved
87…89
Modbus_#_Array
90..109 (# of parameter)
(defaults # are:
1 - Logic Status, 2 - I, 3 - V, 5 – Control In, 11 – Thermistor
Resistance, 37 – Thermal Capacity, 10 – frequency,
4 - Phase
Sequence, 6-Dip Switch, 18 – Total Run Time,
19 – Total Starts, 20-Last Start Period, 21-Last Start Peak I,
22-time to start, 23 – Total Trips, 24-last trip Number, 25 – Pre Trip I,
26 – Time to Reset U/C, 39-Spare, 40-Spare
Notes:
1.
Parameter # is "1 based". The address is 1 lower than parameter #. For example address of parameter
#1 is 0 (40000).
2.
When the Preset Single Register Function (06) is used to adjust one parameter setting, the
communication program checks that the parameter value is within the allowed limits. If not, an
Exception Response (Exception code 03) is returned instead of Normal response. See Exception
Responses later in this document.
3.
If Preset Multiple Register Function (16) is used to adjust one or multiple parameter settings, then even
if one or more parameter settings are out of range, Normal response will be returned.
ASTAT-BP program will check later the value of each parameter. If it is beyond the allowed limit, the
limit value will be stored instead of the transmitted parameter value.