GE Industrial Solutions ASTAT BP User Manual

Page 89

Advertising
background image

ASTAT BP User Manual

89

GE Industrial Solutions

©2013 GE Company All Rights Reserved

Notes:

1. The Read function of the control register is not possible. To read the ASTAT-BP status, read the Logic_Status

(Actual parameter # 1).

2. Bytes 2..8 of the control frame must be exactly as in the following example. Otherwise an error message is

returned.

3. Hardwired Stop and Soft Stop inputs override the communication. To enable motor starting through

communication, terminals 4 and 5 (Stop & Soft stop) must be connected to the control voltage.


Example 5 - Control Register Write:

To start ASTAT-BP # 11, the host computer sends the following Query frame:

byte 1: Serial Link No.

($0B)

byte 2: Function

($10)

Bytes 2..8 must be as in this example!!!

byte 3: Starting Address High ($02)

byte 4: Starting Address Low ($F0)

byte 5: No. of Registers High ($00)

byte 6: No. of Registers Low ($01)

byte 7: Byte Count

($02)

byte 8: Data High

($5A)

byte 9: Data Low

($04)

Bit 2 is set, to start.

byte 10: CRC_Low

($XX)

byte 11: CRC_High

($XX)

The ASTAT-BP Normal response:

byte 1: Serial Link No.

($0B)

byte 2: Function

($10)

byte 3: Starting Address High ($02)

byte 4: Starting Address Low ($F0)

byte 5: No. of Registers High ($00)

byte 6: No. of Registers Low ($01)

byte 7: CRC_Low

($XX)

byte 8: CRC_High

($XX)

A.10.

Discrete Commands (Coils, 0x References)

The ASTAT-BP incorporates 16 "Coils", (bit parameters), of which only 5 are operative. The other 10 are reserved

and were incorporated to enable the user to use word (16 bits) type parameters. Coil # is 1"1 based". The

actual address is 1 lower than coil #. For example coil #1 is addressed as 0 (00000). The coils have the following

0x references:

Coil #

Coil Address

Use in ASTAT-BP

Comment

1

0

Stop

Write "1" (ON) to stop.

2

1

Soft Stop

Write "1" (ON) to Soft Stop

3

2

Start

Write "1" (ON) to start

4

3

Energy Save

Write "1" (ON) to turn On. Write "0" (OFF) to turn Off.

5

4

Dual Adjust

Write "1" (ON) to turn On. Write "0" (OFF) to turn Off.

6

5

Slow Speed

Write "1" for Slow Speed. Write "0" for Normal Start.

7

6

Slow Spd Reverse

Write "1: for Reverse Direction. Write "0" for Forward Direction

8

7

Reset

Write "1" (ON) to Reset.

9..16

8..15

Reserved