TROUBLE SHOOTING

Upon fault – motor stops, the Fault LED lights and Fault Relay chances position. The LCD shows TRIP: < fault

description>. (for example:

Trip: Undercurrent).

Storage Error

Storage Error displays in case of a failure in parameter storing.
Wait 3 seconds and try to store again.

If does not help, load the default parameters of the ASTAT-BP and re-program all

parameters.
To obtain default parameters refer to section 4.5.3 page 21.

Access Locked/
Unauthorized

Access

Avoids parameter changing when

SETTINGS LOCK parameter is set to

PARAMETER LOCKED.
If parameter changing is required set

SETTINGS LOCK parameter to PARAM

NOT LOCKED.
For

SETTINGS LOCK parameter setting refer to section 4.7.2 page 26.

Thermistor Trip Trips the ASTAT-BP when the motor thermistor resistance decreases below trip

level set.
Check resistance of the thermistor and cables; Check motor temperature near

thermistor location.

For

Thermistor Trip protection setting refer to section 4.7.7 page 37.

Too Many Starts Trips the ASTAT-BP if the number of starts, during Duty Cycle Time

exceeds the preset number.
Wait until motor and ASTAT-BP cool down – according to

Number Of Starts,

Duty Cycle Time and Start Lockout settings. Refer to section 4.7.3

page 31.

Long Start Time Trips the ASTAT-BP if output voltage does not reach nominal at the preset Max.

Start time.
Check

Starter Current and Max. Start Time settings. Increase

Starting Voltage, Current Limit & Max. Start Time or decrease

Ramp UP Time as necessary.

For

start Settings Parameters refer to section 4.7.3 page 31.

O/C JAM Fault

Trips the ASTAT-BP when:

Instantaneously when current exceeds 8.5 x ASTAT-BP Current

During starting when current exceeds 8.5 x Motor Current

During running when current exceeds 100-300% of Motor Current.

O/C JAM Fault has a programmable delay of 0-5 seconds where the ASTAT-

BP detects the fault and does not trip before time delay has elapsed (delay is

overriden when current reaches 8.5 x ASTAT-BP Current).

Check that motor is not stalled or jammed.

Check

Motor Current and Starter Current settings.

Check motor and cable connections.

Perform a “Megger” test to verify motor and cable’s condition.

For protection parameters settings refer to section 4.7.2 page 26.

CAUTION

Check that “Megger” maximum voltage is no more than 500V!
Disconnect terminal 21 before performing a “Megger” test.