Notes:
(1)

It is important that the ASTAT-BP is properly grounded and that the control module is tightly fastened to

the power module.

(2)

Use twisted shielded cable for the thermistor connection.

55..77

Remote Key-Pad Installation

Remote key pad cut out; Cable length is 1.5 meters

66..

STARTING PROCEDURE

Note:

It is necessary to connect a motor to load terminals; otherwise

Shorted SCR or WRONG CONNECTION faults are

activated (

OC or Wrong CON.). Other loads such as incandescent light bulbs, resistors, etc. may also cause an OC

or Wrong CON. fault.


WARNING

1

When mains voltage is connected to the ASTAT-BP, even if control voltage is

disconnected, full voltage may appear on the ASTAT-BP load terminals.

Therefore, for isolation purposes, it is necessary to connect an isolating device

upstream to the ASTAT-BP.

2

Power factor correction capacitors must not be installed on the load side of the

ASTAT-BP. When required, install capacitors on the line side of the ASTAT-BP.

3

When using Inside Delta connection, wrong connection of the ASTAT-BP or the

motor may damage the motor; therefore please confirm that the motor is

connected properly!

4

Do not interchange line and load connections

5

Before starting the motor verify its rotation direction. If needed, disconnect the

rotor from the mechanical load and verify the correct direction of rotation.

6

Prior to start up procedure, make sure that line voltage and control voltage

match the ones shown on the name plate of the ASTAT-BP.

7

When the START signal is initiated and a motor is not connected to load

terminals, the

SHORT SCR or WRONG CONNECTION (OC or Wrong CON.)

protection will be activated.