Astat bp user manual – GE Industrial Solutions ASTAT BP User Manual

Page 63

Advertising
background image

ASTAT BP User Manual

63

GE Industrial Solutions

©2013 GE Company All Rights Reserved

88..55

Short Circuit Protection

8.5.1

Standard Short-Circuit Current Ratings for ASTAT BP Soft Starters

Catalog #

Prefix

Frame

FLA

(A)

Short Circuit

Current Ratings

Fuse (Class H, K,

RK5, J or L)

Breaker

Enclosure

Marking

RMS Sym

Amps (A)

Volts Max.

(V)

Max Size (A)

Max Size (A)

Min Volume

(cu-in.)

(a)

(b)

(c)

(d)

(e)

QB20008

D1

8

5000

600

15

30

784

A,B

QB20017

17

5000

600

30

30

784

A,B

QB20031

31

5000

600

60

60

784

A,B

QB20044

44

5000

600

60

60

784

A,B

QB20058

D2

58

10000

600

100

100

1321

A,B

QB20072

72

10000

600

100

100

1321

A,B

QB20085

D3

85

10000

600

200

150

1831

A,B

QB20105

105

10000

600

200

150

1831

A,B

QB20145

D4

145

10000

600

200

250

2565

A,B

QB20170

170

10000

600

400

250

2565

A,B

QB20210

D5

210

18000

600

400

400

17280

A,B

QB20240

240

18000

600

400

400

17280

A,B

QB20310

310

18000

600

600

600

17280

A,B

QB20360

D6

360

18000

600

600

600

17280

A,B

QB20414

414

30000

600

800(Class L)

600

17280

A,B

QB20477

477

30000

600

800(Class L)

600

17280

A,B

QB20515

D7

515

30000

600

1200(Class L)

800

27648

A,B

QB20590

D8

590

30000

600

1200(Class L)

800

27648

A,B

QB20720

D9

720

42000

600

1200(Class L)

1200

33600

A,B

QB20840

840

42000

600

1200(Class L)

1200

33600

A,B

A – The standard Fault Short Circuit Current Rating is required to be marked on the product, or on an

information sheet shipped with the product. The shipping carton may serve as an information sheet.

B – Shall be marked as follows, or equivalent – “Suitable For Use on A circuit capable of Delivering Not more

than (a) RMS symmetrical Amperes, (b) Volts Maximum. Use Fuses Rated (c), or Circuit breakers rated (d)

Amperes Maximum. For use in Enclosures with Minimum over all dimensions

8.5.2

High-Available Fault Short-Circuit Current Ratings for ASTAT BP Soft Starters:

Catalog #

Prefix

Frame

FLA

(A)

Short Circuit

Current Ratings

Fuse

Circuit Breaker

Enclosure

Marking

RMS Sym

Amps (A)

Volts

Max. (V)

Class

Max

Size (A)

Make

Model

Max

Size (A)

Min

Volume

(cu-in.)

(a)

(b)

(c)

(d)

(e)

(f)

(g)

(h)

QB20008

D1

8

100000

600

J

15

-

-

-

784

A,B

QB20017

17

100000

600

J

30

-

-

-

784

A,B

QB20031

31

100000

600

J

60

-

-

-

784

A,B

QB20044

44

100000

600

J

60

-

-

-

784

A,B

QB20058

D2

58

100000

600

J

100

-

-

-

1321

A,B

QB20072

72

100000

600

J

100

-

-

-

1321

A,B

QB20085

D3

85

100000

600

J

200

-

-

-

1831

A,B

QB20105

105

100000

600

J

200

-

-

-

1831

A,B

QB20145

D4

145

100000

600

J

200

-

-

-

2565

A,B

QB20170

170

100000

600

J

400

-

-

-

2565

A,B

QB20210

D5

210

100000

600

J

400

-

-

-

17280

A,B

QB20240

240

100000

600

J

400

-

-

-

17280

A,B

QB20310

310

100000

600

J

600

-

-

-

17280

A,B

QB20360

D6

360

100000

600

J

600

-

-

-

17280

A,B

QB20414

414

100000

600

L

800

-

-

-

17280

A,B

QB20477

477

100000

600

L

800

-

-

-

17280

A,B

QB20515

D7

515

100000

600

L

1200

-

-

-

27648

A,B

QB20590

D8

590

100000

600

L

1200

-

-

-

27648

A,B

QB20720

D9

720

100000

600

L

1200

-

-

-

33600

A,B

QB20840

840

100000

600

L

1200

-

-

-

33600

A,B

Advertising