6.2.2

High Inertia Loads: Crushers, Centrifuges, Mixers, Etc.

(In these cases the actual current is at the

CURRENT LIMIT setting during part of the starting time)

Starting Voltage–

set 40%

Current Limit–

set 400%

Ramp UP Time–

set 3 sec

Upon START the voltage and current increase until the current reaches the

Current Limit value. The

voltage remains at this value until the motor reaches close to nominal speed, where current starts to decrease

and voltage continues to ramp-up to nominal.

6.2.3

Special Starting Using DUAL Settings

Using two starting characteristics, the ASTAT-BP will accelerate using standard characteristics (

Starting

Voltage, Ramp UP Time and Current Limit). After transition (tx), Immediate Relay (RUN relay) ON

Delay, voltage to auxiliary input C1 is switched ON using the DUAL Settings characteristic to complete

acceleration.

Perform the following steps:

Program

PROG.AUX.Relay to IMMEDIATE (default setting), program Relay ON Delay to tx. Refer to

Section 4.7.8 page 39.

Program

PROG. Input C1 to DUAL Settings.Refer to Section 4.7.8 page 39.

Program standard parameters and

DUAL Settings parameters as shown in the table below. Refer to

Section 4.7.5 page 35.

To use

DUAL Settings automatically, connect immediate relay in series to auxiliary input terminal C1 as

shown in section 6.2.3.1 below.

Using two starting characteristics, the ASTAT-BP will accelerate to reach the 200% current limit. After tx

voltage to

PROG. Input C1 is switched ON, using the DUAL Settings characteristic to complete

acceleration.

Parameter

Standard Parameter

DUAL Settings Parameter

Starting Voltage

10%

25%

Ramp UP Time

t1 = 2-30 sec

t2 = 2-30 sec

Current Limit

200%

300-400%

Relay ON Delay

tx = 1-60 sec.

-----