GE Industrial Solutions ASTAT BP User Manual
Page 109
ASTAT BP User Manual
109
GE Industrial Solutions
©2013 GE Company All Rights Reserved
C.6.3.
Common Services
Service
Code
Implemented for
Service Name
Class Level
Instance Level
0E
HEX
Yes
Yes
Get_Attribute_Single
10
HEX
No
Yes
Set_Attribute_Single
C.7.
Softstart Object (2D
HEX
- 1 Instance)
C.7.1.
Class Attributes (Instance 0)
Attribute
ID
Name
DeviceNet
Data Type
Data
Value
Access Rule
1
Revision
UINT
1
Get
C.7.2.
Instance Attributes (Instance 1)
Attribute
ID
Name
Data
Type
Data Value
Access
Rule
Modbus Register
3
AtReference
BOOL
See Below
Get
Bit 11: 40257
4
StartMode
USINT
See Below
Get /
Set
Will Always be 0
C.7.2.1.
Extended AtReference Values
Value
Extended AtReference Description
0
Not At Reference
1
Output At Voltage Reference
C.7.2.2.
Extended StartMode Values
Value
Extended StartMode Description
0
No Voltage Ramp
No Current Limit
1
Voltage Ramp
No Current Limit
2
No Voltage Ramp
Current Limit
3
Voltage Ramp
Current Limit
4 – 9
Reserved
10 - 255
Vendor Specific
C.7.3.
Common Services
Service
Code
Implemented for
Service Name
Class Level
Instance Level
0E
HEX
Yes
Yes
Get_Attribute_Single
10
HEX
No
Yes
Set_Attribute_Single
C.8.
Control Supervisor Object (29
HEX
- 1 Instances)
C.8.1.
Class Attributes (Instance 0)
Attribute
ID
Name
DeviceNet
Data Type
Data Value
Access
Rule
1
Revision
UINT
1
Get