Slow Speed Time Trips the ASTAT-BP when operating at slow speed for extended periods.

Check that operation time at Slow Speed is shorter than

Max Slow Sp Time.

Note: Motor and ASTAT-BP may be overheated when operating at slow speed

for an extended period.

For

Max Slow SP Time protection setting refer to section 4.7.6 page 36.

Wrong

Connection

Trips the ASTAT-BP when one or more motor phases is not properly connected to

ASTAT-BP’s load terminals or if there is an internal disconnection in the motor

winding.


Verify that the motor is connected properly.

See note 1 at the end of this section.

Shorted SCR

Trips the ASTAT-BP and prevents starting if any SCR is short-circuited or

when motor windings are shorted.


Check with an ohmmeter between L1-U, L2-V, L3-W; resistance > 20 K

independent bypass).
SCRs may fail due to:

* High short current not protected by proper fuses
* High voltage spikes not protected by proper external varistors.
* Frequent starting at maximum conditions or fault conditions.

See note 1 at the end of this section.

Over

Temperature

Heat-sink over-temperature. Trips the ASTAT-BP when the heat-sink

temperature rises above 85°C.

Improve cooling or use a bypass contactor. Check that motor starting is not too

frequent.

External Fault Trips the ASTAT-BP when a N.O. contact between terminals A2-C1 closes for

over two seconds. Only applicable if Auxiliary input C1 is set to

External

Fault. Refer to parameter PROG. Input C1 section 4.7.8 page 39

Check contact position and cause of closure.

Wrong

Parameters

Parameters not transferred from RAM to EEPROM or vice versa.

After loading new software version or after power up, press Reset, then Mode
and

▼ simultaneously and save the default parameters by pressing Set and

Mode simultaneously.

(If the Fault LED is ON, press Reset after

Wrong Parameters).

Refer to section 4.4 page 20 for reviewing and modifying parameters.

MODBUS TIME OUT Trips the ASTAT-BP if no valid Modbus communication during Modbus Time Out.

Trip occurs only if the following conditions exist:

• S. Link Control is set to Enabled

• Station Number is not set to OFF

Refer to section 4.7.10 page 41 for reviewing and modifying parameters.

Profi Fault

Command

Trips the ASTAT-BP if, when controlled via Profibus communication link, the

communication cable is torn or the communication from the PLC is lost.