Terminal

Function

Description

Terminals F1,

F2

Fan control

External jumper connected between these terminals will operate

the internal fans.

Applicable in models

QB x 0210 – QB x 1100.

Do not remove this jumper unless factory is consulted.

Terminal B1

Input – START command

4

.

Input from a NO contact.

To SOFT START the motor, close contact between terminals

A2 and B1.

To SOFT STOP the motor open contact between terminal A2 and B1.

If

Ramp DOWN Time is set to a value other than 0 seconds the

motor will soft stop.

If

Ramp DOWN Time is set to 0 seconds the motor will stop

immediately. (Refer to section 4.7.4 on page 33).

If

PROG. Input C1 is set as Start / Stop, then terminal B1 is used

as momentary NO Start input and

PROG. Input C1 is used as

maintained NC Stop input. (Refer to section 4.7.8 on page 39)

For emergency stop of the motor disconnect control voltage from

terminals A1, A2.

Terminal C1

Programmable input – START-

STOP/Reset/External Fault/Slow

Speed /GEN.START-STOP/Dual

Settings

Refer to section 4.7.8 page 39 for

PROG. Input C1

programming.

Terminals 13,

14

Programmable Auxiliary Output

relay (NO):

IMMEDIATE/EOR Relay

Voltage free 8A, 250VAC, 2000VA max.

When set as: Immediate Relay (RUN relay):

• The relay is energized upon the START signal.

• The relay is de-energized when one of the following occurs: Fault,

Control Supply outage or STOP signal.

• When SOFT STOP is operated - the relay is de-energized at the end

of the SOFT STOP process.

• The Immediate Relay (RUN relay) can be used for the following

purposes: Release a brake of a motor, Interlock with other

systems, Signalling, Delay the opening of a line contactor at the

end of SOFT STOP, thus allowing current to decrease to zero

before opening the contactor or to switch to / from DUAL settings

with a time delay from the START signal (see Special Starting

section 6.2.3.1 page 54).

• The relay incorporates ON and OFF delays of 0-60 sec. each.

When set as: EOR Relay (End Of Ramp relay):

• Changes its position at the end of ramp, after an adjustable time

delay (Contact Delay), 0 – 60 sec.

• The contact returns to its original position when Soft Stop or Stop

signals, on Fault condition, or upon voltage outage.

• The EOR (End Of Ramp) contact can be used for: Activating a valve

after compressor has reached full speed or loading a conveyor

after motor reached full speed.

Refer to section 4.7.8 page 39 for

PROG. AUX. RELAY and

Relay ON Delay programming.

Terminals 23,

24

Programmable Fault Output relay

(NO):

At Fault Close/ At Fault

Open.

Voltage free 8A, 250VAC, 2000VA max. changes its position upon

fault.

The contact is programmable to function as

At Fault Close or

At Fault Open.

4

To reset a fault the START command must be removed.