GE Industrial Solutions ASTAT BP User Manual

Page 113

Advertising
background image

ASTAT BP User Manual

113

GE Industrial Solutions

©2013 GE Company All Rights Reserved

Attribute

ID

Name

Range

Default

Value

Access

Rule

Modbus

Address

(Volt)

13

Over voltage DLY

1-10 (Sec)

2

Get/Set

40013

C.11.3.

Common Services

Service

Code

Implemented for

Service Name

Class Level

Instance Level

0E

HEX

Yes

Yes

Get Attribute Single

10

HEX

No

Yes

Set Attribute Single

C.12.

Start Settings Object (72

HEX

– 1 Instance)

C.12.1.

Class Attributes (Instance 0)

Attribute

ID

Name

DeviceNet

Data Type

Data Value

Access

Rule

1

Revision

UINT

1

Get

C.12.2.

Instance Attributes (Instance 1)

Attribute

ID

Name

Range

Default

Value

Access

Rule

Modbus

Address

1

Soft Start Curve

0-10

0

Get/Set

40025

2

Kickstart Time

0-10 (10

th

Sec)

0

Get/Set

40026

3

Starting

Voltage/Current

10-80

30

Get/Set

40027

4

Current Limit

100-500

400

Get/Set

40028

5

Ramp UP Time

1-90

10

Get/Set

40029

6

Max. Start Time

1-250

30

Get/Set

40030

7

Number of Starts

1-10 & 11 - OFF 10

Get/Set

40031

8

Duty Cycle Time

1-60

30

Get/Set

40032

9

Start_Lockout

1-60

15

Get/Set

40033

10

EOR Relay Delay

0-40

5

Get/Set

40034

C.12.3.

Common Services

Service

Code

Implemented for

Service Name

Class Level

Instance Level

0E

HEX

Yes

Yes

Get Attribute Single

10

HEX

No

Yes

Set Attribute Single

C.13.

Stop Settings Object (73

HEX

– 1 Instance)

C.13.1.

Class Attributes (Instance 0)

Attribute

ID

Name

DeviceNet

Data Type

Data Value

Access

Rule

1

Revision

UINT

1

Get

C.13.2.

Instance Attributes (Instance 1)

Attribute

ID

Name

Range

Default

Value

Access

Rule

Modbus

Address

1

Soft Stop Curve

0-10

0

Get/Set

40041

2

Ramp DOWN Time

1-30

10

Get/Set

40042

3

End Torque

0-10

0

Get/Set

40043

Advertising