GE Industrial Solutions ASTAT BP User Manual
Page 113
ASTAT BP User Manual
113
GE Industrial Solutions
©2013 GE Company All Rights Reserved
Attribute
ID
Name
Range
Default
Value
Access
Rule
Modbus
Address
(Volt)
13
Over voltage DLY
1-10 (Sec)
2
Get/Set
40013
C.11.3.
Common Services
Service
Code
Implemented for
Service Name
Class Level
Instance Level
0E
HEX
Yes
Yes
Get Attribute Single
10
HEX
No
Yes
Set Attribute Single
C.12.
Start Settings Object (72
HEX
– 1 Instance)
C.12.1.
Class Attributes (Instance 0)
Attribute
ID
Name
DeviceNet
Data Type
Data Value
Access
Rule
1
Revision
UINT
1
Get
C.12.2.
Instance Attributes (Instance 1)
Attribute
ID
Name
Range
Default
Value
Access
Rule
Modbus
Address
1
Soft Start Curve
0-10
0
Get/Set
40025
2
Kickstart Time
0-10 (10
th
Sec)
0
Get/Set
40026
3
Starting
Voltage/Current
10-80
30
Get/Set
40027
4
Current Limit
100-500
400
Get/Set
40028
5
Ramp UP Time
1-90
10
Get/Set
40029
6
Max. Start Time
1-250
30
Get/Set
40030
7
Number of Starts
1-10 & 11 - OFF 10
Get/Set
40031
8
Duty Cycle Time
1-60
30
Get/Set
40032
9
Start_Lockout
1-60
15
Get/Set
40033
10
EOR Relay Delay
0-40
5
Get/Set
40034
C.12.3.
Common Services
Service
Code
Implemented for
Service Name
Class Level
Instance Level
0E
HEX
Yes
Yes
Get Attribute Single
10
HEX
No
Yes
Set Attribute Single
C.13.
Stop Settings Object (73
HEX
– 1 Instance)
C.13.1.
Class Attributes (Instance 0)
Attribute
ID
Name
DeviceNet
Data Type
Data Value
Access
Rule
1
Revision
UINT
1
Get
C.13.2.
Instance Attributes (Instance 1)
Attribute
ID
Name
Range
Default
Value
Access
Rule
Modbus
Address
1
Soft Stop Curve
0-10
0
Get/Set
40041
2
Ramp DOWN Time
1-30
10
Get/Set
40042
3
End Torque
0-10
0
Get/Set
40043