GE Industrial Solutions ASTAT BP User Manual
Page 107
ASTAT BP User Manual
107
GE Industrial Solutions
©2013 GE Company All Rights Reserved
C.5.3.3.
Input Instance 100 (0x64) – Status
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Slow Speed
Reverse
Reserved Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
1
ASTAT-BP
Tripped
Stopped
Soft Stop
Process
Start Process
Running
Dual_Adjust
On
Energy
Save On
Slow Speed
Forward
C.5.4.
Common Services
Service
Code
Implemented for
Service Name
Class Level
Instance Level
0E
HEX
Yes
Yes
Get_Attribute_Single
10
HEX
Yes
Yes
Set_Attribute_Single
C.6.
Connection Object (05
HEX
– 2 Instances)
C.6.1.
Class Attributes (Instance 0)
Attribute
ID
Name
DeviceNet
Data Type
Data
Value
Access Rule
1
Revision
UINT
1
Get
C.6.2.
Instance Attributes (Instances 1-2) Explicit, Polled I/O
Attribute
ID
Name
DeviceNet
Data Type
Data
Value
Access
Rule
Instance 1
44
Instance 2
45
1
State
USINT
0 = NonExistent
3 = Established
5 = Deferred
Delete
0 = NonExistent
1 = Configuring
3 = Established
4 = Timed Out
Get
2
Instance Type USINT
0
1
Get
3
Transport
Trigger
usint
83
HEX
82
HEX
Get
4
Produced
Connection ID
uint
10xxxxxx011
BIN
xxxxxx
= Node Address
01111xxxxxx
BIN
xxxxxx
= Node Address
Get
5
Consumed
Connection ID
uint
10xxxxxx100
BIN
xxxxxx
= Node Address
10xxxxxx100
BIN
xxxxxx
= Node Address
Get
6
Initial Comm.
Character
USINT
21
HEX
01
HEX
Get
7
Produced
Connection
Size
uint
40
4
Get
8
Consumed
Connection
Size
uint
40
4
Get
9
Expected
Packet Rate
uint
2500 msec
0
Get / Set
12
Watchdog
Timeout
Action
USINT
4 = Deferred
Delete
0 = Timeout
Get / Set
44
Instance 1 is an Explicit Message Connection.
45
Instance 2 is a Polled I/O Message Connection.