GE Industrial Solutions ASTAT BP User Manual

Page 57

Advertising
background image

ASTAT BP User Manual

57

GE Industrial Solutions

©2013 GE Company All Rights Reserved

Overload

Trips the ASTAT-BP when current exceeds the Overload Trip level and the

thermal register has filled up.
Check

Motor Current, Starter Current settings and overload settings

and check motor current, then wait at least 15 minutes to let the motor and

ASTAT-BP cool down before restarting.

For protection parameters settings refer to section 4.7.2 page 26.

Undercurrent

FLT

Trips the ASTAT-BP when line current drops below the preset level for the preset

time.
Check

Undercurrent FLT and Undercurrent DLY settings; check line

currents of L1, L2, L3.

For protection parameters settings refer to section 4.7.2 page 26.

Undervoltage

Trips the ASTAT-BP when line voltage drops below the preset level for the preset

time.
Check

Undervoltage FLT and Undervoltage DLY settings, check line

voltages on L1, L2, L3. When voltage drops to zero, the ASTAT-BP trips

immediately with no delay.

For protection parameters settings refer to section 4.7.2 page 26.

Overvoltage

Trips the ASTAT-BP when line voltage increases above a preset level for a preset

time.
Check

Overvoltage FLT and Overvoltage DLY settings, check line

voltage on L1, L2, L3.

For protection parameters settings refer to section 4.7.2 page 26.

Phase Loss

Trips the ASTAT-BP if 1 or 2 phases are missing.

In cases where the current transformers are connected externally (ASTAT-BP

210-1100A models), verify that that the current transformers are not grounded.

Each current transformer is connected with its 2 wires only and these wires are

not grounded externally.

If previous action does not solve the problem and you are sure that no real

phase loss exists, you can set

Phase Loss protection to Disable.

This situation can occur in rare cases when there is no real fault but the ASTAT-

BP recognizes unusual behaviour like when Total Harmonic Distortion in Voltage

(THDV) in the network is high.

If this is a true case of

Phase Loss then after setting Phase Loss protection

to

Disable the motor will single phase and most likely be tripped by the over

load protection mechanism.

Phase loss might not be detected in motor operating under a light load.

For Phase Loss protection setting refer to section 4.7.7 page 37.

Freq. or ph

loss

Trips the ASTAT-BP if frequency is not in the range of 40-66.6Hz

Check that frequency variations are between 40-66.6Hz.

Phase Sequence

Trips the ASTAT-BP if line phase sequence is wrong.

Check line phase sequence and if wrong, swap two wires on line side. If motor

now rotates in the wrong direction, swap two wires on load side of the ASTAT-

BP.

For

Phase Sequence protection setting refer to section 4.7.7 page 37.

Advertising