GE Industrial Solutions ASTAT BP User Manual

Page 37

Advertising
background image

ASTAT BP User Manual

37

GE Industrial Solutions

©2013 GE Company All Rights Reserved

WARNING!

Operator’s

responsibility!

1. EXPAND SETTINGS are for use in very special applications only!

Do not set EXPAND SETTINGS to Enable unless ASTAT-BP is significantly larger than the motor!

When using EXPAND SETTINGS for the ASTAT-BP

you must be extremely careful to avoid

damaging the motor or ASTAT-BP.

2. Only cancel Phase Loss protection when the operator is sure that no real phase loss exists

and Phase Loss protection is activated. This situation can occur in rare cases when there is no

real fault but the ASTAT-BP recognizes unusual behaviour like when THDV (Total Harmonic

Distortion in Voltage) in the network is high.

If this is a true case of Phase Loss then after cancelling Phase Loss protection the motor will

single phase and most likely be tripped by the over load protection mechanism.

4.7.7

Fault Settings

32

– Page 6

Function &

Default

Range

Unit

Description

Phase Loss

Enabled

Enabled

33

Sets Phase Loss trip

Phase Loss protection trips the ASTAT-BP when 1 or 2

phases are missing.

Notes:

If ASTAT-BP trips on

Phase Loss do the following:

(4)

In cases where the current transformers are

connected externally (QBx0210-QBx1100 models),

verify that that the current transformers are not

grounded. Each current transformer is connected

with its 2 wires only and these wires are not

grounded externally.

(5)

If previous action does not solve the problem and

the you are sure that no real phase loss exists, you

can set Phase Loss protection to

Disable.

This situation can occur in rare cases when there is

no real fault but the ASTAT-BP recognizes unusual

behaviour like when Total Harmonic Distortion in

Voltage (THDV) in the network is high.

(6)

If this is a true case of

Phase Loss then after

setting

Phase Loss protection to Disable the

motor will single phase and most likely be tripped

by the over load protection mechanism.

(7)

Phase loss might not be detected in motor

operating under a light load.

WARNING

Do not set

Phase Loss to Disable unless it is found

to be necessary in the field!

Phase Sequence

Disabled

Enabled/

Disabled

Sets Phase Sequence trip

When ASTAT-BP is connected in

DELTA Conf. you can

not set

Phase Sequence protection to Disabled.

32

Displays in MAXIMIZED MODE only. To change to this mode refer to parameter DISPLAY MODE on section 4.7.2 page 26.

33

The range of the PHASE LOSS can be extended to Enabled or Disabled by using the EXPANDED SETTING as described in

section 4.7.6 page 36.