ASTAT BP User Manual

31

GE Industrial Solutions

©2013 GE Company All Rights Reserved

Function &

Default

Range

Unit

Description

Max. Start Time

30 SEC.

1-60

sec.

Sets Maximum Start Time

The maximum allowable start time, from the start signal to the

end of the acceleration process. If voltage/speed does not reach

nominal during

Max. Start Time then ASTAT-BP will trip the

motor and create a fault. The LCD will display the

Long Start

Time fault message.

For example, this can occur when the

Current Limit setting

is too low.

Notes:

When

Overload Class is set to NEMA Class 10 Max.

Start Time can be set to 15 seconds maximum.

When

Overload Class is set to IEC Class 10 or NEMA

Class 20 Max. Start Time can be set to 30 seconds

maximum.

When

Overload Class is set to IEC Class 20 or NEMA

Class 30 Max. Start Time can be set to 60 seconds

maximum with limitation automatically calculated by the soft

starter.

Number of Starts

10

1-10, OFF

Sets Number of Starts permitted during Duty Cycle Time (see

below).

Limits the

Number of Starts during the period of time

defined by

Duty Cycle Time.

If you try to start even one more time within that period the

START Lockout period will take effect.

Duty Cycle Time

30 Min.

1–60

min.

Sets Duty Cycle Time during which Number of Starts is counted.

During the

START Lockout period the Wait before RST

XX Min message will be displayed.

Start Lockout

15 Min.

1–60

min.

Sets START Lockout time during which starting is disabled after

Too Many Starts trip.

Store Settings

Start Settings

Same as

Store Settings Main Settings on page 28.

44..77..33..11

Soft Start Parameters

The ASTAT-BP incorporates five starting curves to enable you to select a suitable torque curve.

Soft Start Curve 0 – Standard curve (Default). This curve is the most suitable curve

for preventing prolonged starting and motor overheating.


Note:

When ASTAT-BP is connected in

DELTA Conf., the ASTAT-BP will always use Curve 0

regardless of the curve defined.