Press the

▲ key. The LCD will display:

Self Test Passed

And after a few seconds the LCD will display:

Motor Current

I<0.1 Ir

4.5.2

View Software Version

Press the Mode and

▼ keys simultaneously. The LCD will display:

Test/Maintenance

Statistics

Press the Select key twice. The LCD will display:

Firmware Version

STRT.GEX-050312

Press the Mode and

▼ keys simultaneously to exit the Test/Maintenance mode. The LCD will display:

Motor Current

I<0.1 Ir

4.5.3

Obtain Default Parameters

Press the Mode and

▼ keys simultaneously. The LCD will display:

Test/Maintenance

Statistics

Press the Select key three times. The LCD will display:

Store Settings

Default data

Press the Set + Mode keys simultaneously. The LCD will display:

Data Saved OK

And after a few seconds the LCD will display:

Motor Current

I<0.1 Ir

CAUTION!

Obtaining Default Data erases all previously modified settings and requires the

operator to reprogram all parameters that differ from the factory default.

Note: It is especially important to reprogram the

Starter Current (as shown

on the name plate of the ASTAT-BP),

Motor Current and voltage protection

values again.

4.5.4

Reset Statistical Data

Press the Mode and

▼ keys simultaneously. The LCD will display:

Test/Maintenance

Statistics

Press the Select key four times. The LCD will display:

Reset Statistics

Press the Reset + Set keys simultaneously. The LCD will display:

Data Saved OK

And after a few seconds the LCD will display:

Statistical Data

- **** -

Press the Mode and go back to:

Motor Current

I<0.1 Ir