Push-Buttons
Mode
Scrolls through the display and programming menus of the ASTAT-BP.
6
Select
When a mode name is displayed, pressing this button drills down to the parameters for that mode.
When a parameter is displayed, pressing this button scrolls to the next parameter.
▲
Allows the operator to increment adjusted values shown in the display. Operator should press this
button once to increment one value, or continuously to rapidly increment values up to the maximum
value.
▼
Allows the operator to decrement adjusted values shown in the display. Operator should press this
button once to decrement one value, or continuously to rapidly decrement values up to the minimum
value.
Set
Stores modified parameters only when you have scrolled through all parameters and
Store
Settings Xxxxxx Parameters is displayed. After you store a parameter successfully Data
Saved OK will display.
7
Reset
Resets the ASTAT-BP after a fault has been dealt with and the start command has been removed. This
cancels the fault displayed and allows you to restart the motor.
44..33
Status LEDs
Green
On
Lights when the control supply voltage is connected to the ASTAT-BP.
Yellow
Ramp
8
Lights during soft start, indicating that motor supply voltage is ramping up or
down.
Green
Run
Lights after completion of the starting process, indicating that motor is receiving
full voltage. This LED flashes during slow speed operation.
Red
Fault
Lights upon operation of any of the built-in protections.
44..44
Reviewing and Modifying Parameters
Press the Mode key several times until you reach the required mode page.
Press the Select key to review parameters for this mode.
Once you reach the required parameter, use the
▼ or ▲ keys to modify its value.
To store the new parameters, press the Select key until the
Store Settings Xxxxxx Parameters message
displays and then press the Set key. The
Data Saved OK message will display for 2 seconds.
Note:
After completing parameter settings:
•
Turn control voltage OFF
•
Wait 3 seconds
•
Reconnect control voltage
•
Verify that all parameters are set correctly.
44..55
Special Actions Performed in Test/Maintenance Mode
4.5.1
Run Self Test
Press the Mode and
▼ keys simultaneously. The LCD will display:
Test/Maintenance
Statistics
Press the Select key. The LCD will display:
Auto Test.
Press UP Key
6
Pressing Mode continuously increases the speed at which the parameters change.
7
Pressing the Set button at any other time has no effect.
8
Ramp LED does not exist in the remote keypad. Instead, the RUN LED flashes during Soft Start, Soft Stop and slow speed operation.