4.7.6

Slow Speed & Expnd Parameters

30

– page 5

Function &

Default

Range

Unit

Description

Slow Speed TRQ.

8

1(MIN.) –

10(MAX.)

Sets Slow Speed Torque.

Determines the torque while motor is operating at 1/6 of

nominal speed. Refer to section 4.7.8.1 on page 41.

Max Slow SP Time

30 SEC.

1-30sec.

31

Sets the maximum time for Slow Speed Torque operation.

Determines the maximum allowable operation time at slow

speed.

ASTAT-BP will trip when this time is exceeded and a

Slow

Speed Time message will display.

WARNING

Operating current while motor is running at 1/6 speed is

much higher than nominal current and motor ventilation is

much weaker. Special caution must be taken to prevent

overheating when running the motor at slow speed for long

periods of time.

EXPAND SETTINGS

Disabled

Enabled/

Disabled

Sets some parameters limits. Refer to section 4.7.6.1 below.

Store Settings

Slow SP & Expnd

Same as

Store Settings Main Settings on page 28.

44..77..66..11

EXPAND SETTINGS

Parameter

EXPAND SETTINGS Disabled

EXPAND SETTINGS Enabled

Starting Voltage

10-50%

5

(1)

-80%

Current Limit

100-400%

100-500%

Ramp UP Time

1-30 seconds

1-90 seconds

Ramp DOWN Time

0-30 seconds

0-90 seconds

Max. Star Time

1-30 seconds

1-250 seconds

Phase Loss

Enabled

(2)

Enabled / Disabled

(2)

Max Slow SP Time

1-30 seconds

1-250 seconds

O/C or WR. CON protection in

Inside Delta mode.

Protection active in normal set

(3)

Protection active in high set

(3)

Notes:

(1)

Setting the

Starting Voltage to lower than 10% is not practical for loaded motors.

(2)

Refer to section 7 page 56. See

Phase Loss protection and refer to the warning below.

(3)

Refer to section 7 page 56. See

OC or Wrong CON. protection.

30

Displays in MAXIMIZED MODE only. To change to this mode refer to parameter DISPLAY MODE on section 4.7.2 page 26.

31

The range of the Max Slow SP Time can be extended to 1-60 by using the EXPANDED SETTING as described in section 4.7.6 page 36.