GE Industrial Solutions ASTAT BP User Manual
Page 111
ASTAT BP User Manual
111
GE Industrial Solutions
©2013 GE Company All Rights Reserved
Attribute
ID
Name
DeviceNet
Data Type
Data Value
Access
Rule
111
Number of Write Errors
(since power up)
UDINT
0
Get
112
Number of Write Timeouts
(since power up)
UDINT
0
Get
C.9.3.
Common Services
Service
Code
Implemented for
Service Name
Class Level
Instance Level
0E
HEX
Yes
Yes
Get Attribute Single
10
HEX
No
Yes
Set Attribute Single
32
HEX
No
Yes
Clear Counters
C.10.
Input Object (70
HEX
–
1 Instance)
C.10.1.
Class Attributes (Instance 0)
Attribute
ID
Name
DeviceNet
Data Type
Data Value
Access
Rule
1
Revision
UINT
1
Get
C.10.2.
Instance Attributes (Instance 1)
Attribute
ID
Name
Description
Access
Rule
Modbus
Address
1
Logic Status
Logic Status of ASTAT-BP:
Get
40257
2
Motor Current
Current, % Im
Get
40258
3
Line Voltage
Line Voltage (Volts)
Get
40259
4
Phase Sequence
1 – Correct Phase Seq.
0 – Wrong Phase Seq.
Get
40260
5
Hardwired inputs
Get
40261
6
DIP switch
Get
40262
7
Thermal Capacity
Get
40293
8
Reserved
Get
40264
9
Reserved
Get
40265
10
Frequency
Main frequency, Hz
Get
40266
11
Thermistor_
Resistance
Thermistor resistance, tenth
Kohm.
Get
40267
12
Reserved
Get
40268
13
Reserved
Get
40269
14
Reserved
Get
40270
15
Reserved
Get
40271
16
Reserved
Get
40272
17
Logic status at
power fail
Logic status at control power
supply turns OFF.
Get
40273
18
Elapsed Run Time
Total Hours of motor runs.
Get
40274
19
Number of Starts
Total number of starts
Get
40275
20
Last start period
Duration of last start, Seconds Get
40276
21
Last start peak I
Peak current during last
starting process
Get
40277
22
Time_to_Start
After too many starts trip,
Seconds
Get
40278
23
Total trips
Total number of trips
Get
40279
24
Last Fault number # of the fault that caused trip.
# Fault
01: Over Temperature
Get
40280