ASTAT BP User Manual

85

GE Industrial Solutions

©2013 GE Company All Rights Reserved

A.8.

Parameter Settings (4X References)

Parameter settings include all parameters that can be set manually. These parameters determine the modes

of operation of the ASTAT-BP. They also set protections level. All parameters are word (two bytes) parameters.

The protocol supports both reading and modifying of (most of) these parameters.

All of these parameters must be set with care. Inappropriate settings of some parameters can result in damage

to both the motor and the ASTAT-BP.

The parameters have the following 4x references:
Note: Use function 3 to read the parameter settings.

Parameter

#

Range

Default

Main Settings

Starter Current

1

8..1400

58 (Amp.)

Motor Current

2

4..4000

58 (Amp.)

Line/Delta Configuration

3

0 (Line), 1(Inside Delta)

0 (Line)

Undercurrent_FLT

4

0..90

0 (% of Im)

Undercurrent_DLY

5

1..40

10 (Seconds)

O/C JAM Fault

6

100..850

400 (% of Im)

O/C JAM Delay

7

0..50

5 (0.5 Sec.)

Overload_Class

8

0-iec 10, 1-iec 20,

0-iec 10

2-nema 10, 3-nema 20,

4-nema 30

Overload_Protect

9

0-Disable, 1-Enable after EOR

1-Enabled

2-Enable

Undervoltage_FLT

10

120..600

300 (Volt)

UnderVoltage_DLY

11

1..10

5 (Seconds)

Overvoltage_FLT

12

150..750

480 (Volt)

Overvoltage_DLY

13

1..10

2 (Seconds)

Reserved

14..24

Start Settings

Soft Start Curve

25

0..10 (5..9 are reserved)

0 (Standard).

Kickstart Time

26

0..10 (Tenth Seconds)

0 (No Pulse)

Starting Voltage/Current

27

10..80

30 (% of full voltage)

Current Limit

28

100..700

400 (% of Im)

Ramp UP Time

29

1..90

10 (Seconds)

Max. Start Time

30

1..60

30 (Seconds)

Number of Starts

31

1..10 & (11 = OFF)

10

Duty Cycle Time

32

1..60

30 (Minutes)

Start_Lockout

33

1..60

15 (Minutes)

EOR Relay Delay

34

0..40

5 (Seconds)

Reserved

35..40

Stop Settings

Soft Stop Curve

41

0..10 (5..9 are for reserved)

0 (Standard)

Ramp DOWN Time

42

1..30

10 (Seconds)

End Torque

43

0..10

0 (Minimum)

Reserved

44..48

DUAL Settings

Starting VOLT-2

49

10..80 %, 100-400

30

Current Limit-2

50

100..700

300 % of Im

Ramp UP-2

51

1..90

10 (Seconds)

Ramp DOWN-2

52

1..30

10 (Seconds)

Motor Current-2

53

5..1400

31 (Amp.)

Reserved

54..56