A.8.
Parameter Settings (4X References)
Parameter settings include all parameters that can be set manually. These parameters determine the modes
of operation of the ASTAT-BP. They also set protections level. All parameters are word (two bytes) parameters.
The protocol supports both reading and modifying of (most of) these parameters.
All of these parameters must be set with care. Inappropriate settings of some parameters can result in damage
to both the motor and the ASTAT-BP.
The parameters have the following 4x references:
Note: Use function 3 to read the parameter settings.
Parameter
#
Range
Default
Main Settings
Starter Current
1
8..1400
58 (Amp.)
Motor Current
2
4..4000
58 (Amp.)
Line/Delta Configuration
3
0 (Line), 1(Inside Delta)
0 (Line)
Undercurrent_FLT
4
0..90
0 (% of Im)
Undercurrent_DLY
5
1..40
10 (Seconds)
O/C JAM Fault
6
100..850
400 (% of Im)
O/C JAM Delay
7
0..50
5 (0.5 Sec.)
Overload_Class
8
0-iec 10, 1-iec 20,
0-iec 10
2-nema 10, 3-nema 20,
4-nema 30
Overload_Protect
9
0-Disable, 1-Enable after EOR
1-Enabled
2-Enable
Undervoltage_FLT
10
120..600
300 (Volt)
UnderVoltage_DLY
11
1..10
5 (Seconds)
Overvoltage_FLT
12
150..750
480 (Volt)
Overvoltage_DLY
13
1..10
2 (Seconds)
Reserved
14..24
Start Settings
Soft Start Curve
25
0..10 (5..9 are reserved)
0 (Standard).
Kickstart Time
26
0..10 (Tenth Seconds)
0 (No Pulse)
Starting Voltage/Current
27
10..80
30 (% of full voltage)
Current Limit
28
100..700
400 (% of Im)
Ramp UP Time
29
1..90
10 (Seconds)
Max. Start Time
30
1..60
30 (Seconds)
Number of Starts
31
1..10 & (11 = OFF)
10
Duty Cycle Time
32
1..60
30 (Minutes)
Start_Lockout
33
1..60
15 (Minutes)
EOR Relay Delay
34
0..40
5 (Seconds)
Reserved
35..40
Stop Settings
Soft Stop Curve
41
0..10 (5..9 are for reserved)
0 (Standard)
Ramp DOWN Time
42
1..30
10 (Seconds)
End Torque
43
0..10
0 (Minimum)
Reserved
44..48
DUAL Settings
Starting VOLT-2
49
10..80 %, 100-400
30
Current Limit-2
50
100..700
300 % of Im
Ramp UP-2
51
1..90
10 (Seconds)
Ramp DOWN-2
52
1..30
10 (Seconds)
Motor Current-2
53
5..1400
31 (Amp.)
Reserved
54..56