GE Industrial Solutions ASTAT BP User Manual

Page 88

Advertising
background image

ASTAT BP User Manual

88

GE Industrial Solutions

©2013 GE Company All Rights Reserved

Example 4:

To write multiple parameter settings (Undervoltage_FLT = 300V, Undervoltage_DLY = 10Sec, Overvoltage_FLT =

480V, Overvoltage DLY = 2Sec) to Parameter settings # 10-13(Addressed as 9-12) of ASTAT-BP # 128, the host

computer sends the following frame:

byte 1: Serial Link No.

($80)

byte 2: Function

($10)

byte 3: Starting Address High ($00)

byte 4: Starting Address Low ($09)

byte 5: No. of Registers High ($00)

byte 6: No. of Registers Low ($04)

byte 7: Byte Count

($08)

byte 8: Data High

($01)

(300)

byte 9: Data Low

($2C)

byte 10: Data High

($00)

(10)

byte 11: Data Low

($10)

byte 12: Data High

($01)

(480)

byte 13: Data Low

($E0)

byte 14: Data High

($00)

(2)

byte 15: Data Low

($02)

byte 16: CRC_Low

($XX)

byte 17: CRC_High

($XX)

The ASTAT-BP Normal response:

byte 1: Serial Link No.

($80)

byte 2: Function

($10)

byte 3: Starting Address High ($00)

byte 4: Starting Address Low ($09)

byte 5: No. of Registers High ($00)

byte 6: No. of Registers Low ($04)

byte 7: CRC_Low

($XX)

byte 8: CRC_High

($XX)


Note:

A Normal response will be returned even if the preset data value is beyond the allowed range for one or more

parameter settings. Later the ASTAT-BP program will check the value of each parameter. If it exceeds the

allowed limit, the limit value will be stored instead the transmitted parameter value. It is the user’s

responsibility to read and check all parameter settings after presetting.

A.9.

Control Register Write (4X Reference)

The ASTAT-BP incorporates one Control register intended for controlling the ASTAT-BP.

Address: The Control register is register # 753 addressed as 752 (40752).

In order to control the ASTAT-BP uses the Control register:

* Use Function 16 only.

* Use Address_High (page) = 2

* Use Address_Low = 240 (0F0H).

* Write to one register only.

* Use data_high (ms-byte of data) = 5AH.

* Data_low Bits resolution of the control register (ls-byte of data):


bit

function

Comment

d0

Stop

Write "1" (ON) to stop.

d1

Soft Stop

Write "1" (ON) to Soft Stop

d2

Start

Write "1" (ON) to start

d3

Energy Save

Write "1" (ON) to turn On. Write "0" (OFF) to turn Off.

d4

Dual Adjust

Write "1" (ON) to turn On. Write "0" (OFF) to turn Off.

d5

Slow Speed

Write "1" for Slow Speed. Write "0" for Normal Start.

d6

Slow Spd Reverse

Write "1: for Reverse Direction. Write "0" for Forward Direction

d7

Reset

Write "1" (ON) to Reset.

Advertising