GE Industrial Solutions ASTAT BP User Manual
Page 13
ASTAT BP User Manual
13
GE Industrial Solutions
©2013 GE Company All Rights Reserved
33..22
Weight
Model
Weight
Kg
Lbs
QBx0008xxxxx
3
6.6
QBx0017xxxxx
3
6.6
QBx0031xxxxx
3
6.6
QBx0044xxxxx
3
6.6
QBx0058xxxxx
5.2
11.4
QBx0072xxxxx
5.2
11.4
QBx0085xxxxx
8.5
18.7
QBx0105xxxxx
8.5
18.7
QBx0145xxxxx
12.5
27.6
QBx0170xxxxx
12.5
27.6
QBx0210xxxxx
37
81.6
QBx0240xxxxx
37
81.6
QBx0310xxxxx
37
81.6
QBx0360xxxxx
38
83.8
QBx0414xxxxx
38
83.8
QBx0477xxxxx
38
83.8
QBx0515xxxxx
42.2
93
QBx0590xxxxx
50.6
111.5
QBx0720xxxxx
54
119
QBx0840xxxxx
54
119
QBx0960xxxxx
75.5
166.4
QBx1100xxxxx
75.5
166.4
33..33
I/O Terminal Board Specifications
Refer to drawing on page 16.
Terminal
Function
Description
1L1, 3L2, 5L3
Connection to mains voltage up to
600V
Thyristor’s PIV rating, internal circuitry and insulation defines three
voltage levels:
QB 1 x : for 208-400V +10%/ -15% 50/60Hz
QB 2 x: for 440-600V +10% /-15% 50/60Hz
Each ASTAT-BP is suitable for one of the above levels & for 50/60 Hz.
2T1, 4T2, 6T3
Connection to motor
Connect motor’s terminals to these terminals/busbars.
G
Connection to ground
For proper operation and for safety reasons soft ASTAT-BP must be
properly grounded.
Terminal A1
Control phase
The control voltage operates the electronic circuitry and the fans
(when they exist).
Terminal A2
Control neutral (return)
Two control voltages are available:
QB x xxxx 1 x x S for 110V +10%/-15% 50/60Hz
QB x xxxx 2 x x S for 230V +10%/-15% 50/60Hz