Note:

Resetting of all faults, except for

Undercurrent protection, (Local, Remote, Serial Link or Auto Reset) is not

possible as long as the START signal exists.

4.8.9

Auto Reset

Undervoltage and Phase Loss faults can auto-reset (refer to section 4.7.7 on page 37). The ASTAT-BP will

reset itself 60 seconds after voltage was fully restored, provided that the START signal is removed.

Undercurrent fault can be set to auto-reset (refer to section 4.7.7 on page 37).

The ASTAT-BP will reset itself when a programmed time delay has elapsed, even if the START signal is not

removed.

44..99

Timing Occurrence Table

Timing And Occurrence

Active During

Start

Run

Stop

Soft

Stop

Too many starts with Start Lockout period

Electronic overload with curve selection

37

O/C JAM Fault
ASTAT-BP protection – trip immediately at I≥850% Starter

Current

Motor protection – trip function
During start – factory set at 850% Motor Current after O/C

JAM Delay.

During run – adjustable 100 – 300% Motor Current after O/C

JAM Delay.

Undercurrent adjustable time delay

Phase Loss

Phase Sequence

Undervoltage with adjustable time delay. Time delay is

override in case of Phase Loss.

Overvoltage with adjustable time delay

Long start time (stall protection)

Shorted SCR

Wrong Connection (load loss)

External fault – input from a N.O. contact

SCR protection by Metal Oxide Varistors (MOV)

ASTAT-BP over-temperature

ASTAT-BP internal test, when the On LED is lit.

Motor thermistor – programmable PTC/NTC, with adjustable

trip level.

37

Timing Occurrence depends on the setting of Overload Protect. Refer to section 4.7.2 page 26.