GE Industrial Solutions ASTAT BP User Manual

Page 47

Advertising
background image

ASTAT BP User Manual

47

GE Industrial Solutions

©2013 GE Company All Rights Reserved

55..

INSTALLATION

WARNINGS

Do not interchange line and load connections

When mains voltage is connected to the ASTAT-BP, even if control voltage is

disconnected, full voltage may appear on the ASTAT-BP’s load terminals.

Therefore if isolation is required you must connect an isolation device between the

mains and the ASTAT-BP.
Power factor correction capacitors must not be installed on the load side of the

ASTAT-BP. When required, install capacitors on the line side of the ASTAT-BP.

55..11

Prior to Installation

Check that the Full Load Ampere (Im) of the motor is lower than or equal to the Current Rating in the expected

load duty (LD or HD) indicated on the side and/or front name plate of the ASTAT-BP.

Note that Current Rating indicated as LD corresponds to load duty NEMA Class 10; Current Rating indicated as

HD corresponds to load duty IEC Class 20 or NEMA Class 30.

Also verify that the mains voltage, Control Voltage and Control Input voltage are as indicated on the name

plate of the ASTAT-BP.

Verify that motor current and load duty (LD or HD)

matches the Current Rating indication.

Verify mains voltage is correct!

Verify that Control Voltage (terminals A1, A2) is correct!

ASTAT-BP name plate - example

55..22

Mounting

The ASTAT-BP must be mounted vertically. Allow sufficient space for suitable airflow above and below the

ASTAT-BP. To improve heat dissipation, it is recommended that you mount the ASTAT-BP directly on the rear

metal plate.

Notes:

(8)

Do not mount the ASTAT-BP near heat sources.

(9)

Surrounding air temperature in the cabinet should not exceed 50°C

(10)

Protect the ASTAT-BP from dust and corrosive atmospheres.

55..33

Temperature Range & Heat Dissipation

(11)

The ASTAT-BP is rated to operate within a temperature range of -10°C (14°F) to + 60°C (122°F).

Relative non-condensed humidity inside the enclosure must not exceed 95%.

ATTENTION

Operating the ASTAT-BP with a surrounding air temperature that is higher than

50°C and up to 60°C, derate the current by 2.5% for each °C that is above 50°C.

CAUTION

Operating the ASTAT-BP with a surrounding air temperature that is higher than

60°C may cause damage to the ASTAT-BP.