A – The High–Available Fault Short Circuit Current Rating is optionally marked on the product, or on an

information sheet shipped with the product. The shipping carton may serve as an information sheet.

B – When marking is provided, it shall be as follows, or equivalent – “Suitable for use on a Circuit Capable of

Delivering Not More Than (a) RMS Symmetrical Amperes, (b) Volts maximum When Protected by (c) Class

Fuses Rated (d) Amperes Maximum. For Use In Enclosures With Minimum Overall Dimensions of (h).”

C – When marking is provided, it shall be as follows, or equivalent – “Suitable For Use on A Circuit Capable of

Delivering Not More Than (a) RMS Symmetrical Amperes, (b) Volts Maximum When Protected by (e) Type (f)

Circuit Breakers, rated (g) Amperes Maximum. For Use In Enclosures With Minimum Overall Dimensions of

(h).”

Note:

QB* – ASTAT BP Range

88..66

Transient Protection

Line transient voltages can cause a malfunction of the ASTAT-BP and damage to the thyristors. All ASTAT-BPs

incorporate Metal Oxide Varistors (MOV) to protect from normal line voltage spikes.