ASTAT BP User Manual

82

GE Industrial Solutions

©2013 GE Company All Rights Reserved

A.6.

List of Functions Supported By The ASTAT-BP

Function

Modbus Name

Use in ASTAT-BP

01

Read Coil Status Read discrete commands status.

02

Read Input Status

Read discrete inputs status.

03

Read Holding Registers.

Read setting parameters.

Read actual data (for Modbus Plus users).

04

Read Input Registers.

Read actual data.

05

Force Single Coil.

Force one discrete command.

06

Preset Single Register.

Write one parameter setting.

08

Diagnostics.

Loopback diagnostics.

15

Force Multiple Coils.

Force discrete commands.

16

Force Multiple Registers

Write parameter setting

Control commands

DATA

Data field includes information transferred to and from the ASTAT-BP. The specific data format is changed with

Function. When Word data parameters are transmitted, High Byte is transmitted first, followed by the Low

Byte.


CRC

The CRC (Cyclic Redundancy Check) two bytes (16 bit) are used to check the bytes of the entire frame.

It is generated in the master device and transmitted as the last two bytes of the frame (Low byte is appended

first, followed by the High byte). The slave device regenerates the CRC bytes and compares it to the CRC bytes

received. If the CRC bytes are not identical, the frame is flushed and no response is transmitted to the master.


ASTAT-BP MEMORY ORGANIZATION

The ASTAT-BP memory is organized according to the common Modbus addresses as follows:


ASTAT-BP Use

Memory Type

Max Query/Response Parameters

Actual Data

3X References Registers,

# 1...128, addressed 0..127.

4X References Registers,

#257...384 addressed. 256...383

Setting Parameters

4X References Registers,

# 1...109, addressed 0...108

Hardwired Control Inputs

1X References 16 Inputs,

# 1..16, addressed 0..15.

Discrete Serial Commands

0X References 16 Coils,

# 1..16, addressed 0..15.

Control Commands

4X References 1 Register,

# 753, addressed 752.


Notes:
1. Actual Data parameters can be read both at 3X references starting at parameter #1, or (same parameters)

at 4X references starting at parameter #257 (100 hex higher). The additional mapping in 4X references is

designed for the convenience of Modbus Plus users.

2. ASTAT-BP can be controlled using the standard discrete commands (Coils, 0x references) or by writing to

parameter setting #753 with function 16. The additional control option using 4X references is designed for the

convenience of Modbus Plus users. To control, write to register #753 (address 752) only! (one register write,

with function 16).

3. Function 3 should be used to read 4X references. Function 4, to read 3x references.