GE Industrial Solutions ASTAT BP User Manual

Page 27

Advertising
background image

ASTAT BP User Manual

27

GE Industrial Solutions

©2013 GE Company All Rights Reserved

Function &

Default

Range

Unit

Description

O/C JAM Fault

200% of Im

100-300

% of

Motor

Current

Sets O/C JAM Fault protection.

Operational when ASTAT-BP is energized and has three trip

functions:

At all time - If I > 850% of

Starter Current it trips the

ASTAT-BP within 1 cycle (overrides the value of the

O/C JAM

Fault setting).

O/C JAM Delay

0.5 Sec.

0.0 – 5

sec.

At starting process - If I > 850% of

Motor Current it trips

the ASTAT-BP after

O/C JAM Delay

At run time - If I >

O/C JAM Fault setting of Motor

Current it trips the ASTAT-BP after O/C JAM Delay.

Caution:

The

O/C JAM Fault is not intended to replace the fast

acting fuses, required to protect the thyristors. Refer to

section 8.5 on page 63.

Overload Class

IEC CLASS 10

IEC CLASS 10;

IEC CLASS 20;

NEMA CLASS

10;

NEMA CLASS

20;

NEMA CLASS

30;

Sets Overload CLASS.

Overload Class is operational as programmed in the

Overload Protect parameter. (see next parameter)

The O/L circuitry incorporates a thermal memory register

that calculates heating minus dissipation of the motor. The

ASTAT-BP trips when the register fills up.

The time constant for cool down after overload trip is:

For IEC/NEMA Class 10 – 320seconds

For IEC/NEMA Class 20 – 640seconds

For NEMA Class 30 – 960seconds

Refer to section 2.4 on page 10 for thermal characteristic.

Note:

When setting

Motor Current to a higher level than

Starter Current, Overload Class parameter is

automatically set to

NEMA Class 10.

Overload Protect

Enabled

Enable after

EOR;

Enabled;

Disabled;

Sets Overload Protection operation.

Enable after (End Of Ramp) will set the overload

protection to be operative after starting process is completed

and (End Of Ramp) relay is energized.

Enabled will set the overload protection to be operative at

all time.

Disabled will set the overload protection not to be

operative at all time.
ATTENTION!

When

Overload Protect is set to Disabled the motor

is not protected for Overload!!

Undervoltage FLT

75%

50-90

% of

mains

voltage

Sets Undervoltage Fault level.

Trips the ASTAT-BP when mains voltage drops below the level

that was set for a time longer than

Undervoltage DLY.

Undervoltage DLY

5 SEC.

1 –10

sec.

Sets Undervoltage Fault delay

16

16

Becomes operational only after the start signal.

When voltage drops to zero (voltage outage) the ASTAT-BP will trip immediately, thus overriding the delay.