GE Industrial Solutions ASTAT BP User Manual

Page 110

Advertising
background image

ASTAT BP User Manual

110

GE Industrial Solutions

©2013 GE Company All Rights Reserved

C.8.2.

Instance Attributes (Instance 1)

Attribute

ID

Name

DeviceNet

Data Type

Data

Value

Access

Rule

Modbus Register

3

Run1 (Forward)

BOOL

0

Get / Set Bit 2: 40752

Bit 8-15: 0x5A

4

Run2 (Reverse)

BOOL

0

Get / Set Always 0

7

Running1

(Forward)

BOOL

0

Get

Bit 11: 40257

9

Ready

BOOL

0

Get

Bit 5: 40257

10

Faulted

BOOL

0

Get

Bit 15: 40257

11

Warning

BOOL

0

Get

Bit 6: 40257

15

Ctrl From Net

BOOL

1

Get

Always 1

100

Control Word

UINT

0

Get / Set 40752

(Read always 0-

since register is

not readable)

C.8.3.

Common Services

Service

Code

Implemented for

Service Name

Class Level

Instance Level

05

HEX

No

Yes

Reset

0E

HEX

Yes

Yes

Get Attribute Single

10

HEX

No

Yes

Set Attribute Single

C.9.

Modbus / Serial Object (65

HEX

– 1 Instance)

C.9.1.

Class Attributes (Instance 0)

Attribute

ID

Name

DeviceNet

Data Type

Data Value

Access

Rule

1

Revision

UINT

1

Get

C.9.2.

Instance Attributes (Instance 1)

Attribute

ID

Name

DeviceNet

Data Type

Data Value

Access

Rule

1

Modbus Slave ID (1-247)

USINT

1

Get /

Set

47

2

Baud Rate

0 = 4800

1 = 9600

2 = 19200

USINT

2

Get /
Set

47

3

Parity

0 = 8N

1 = 8E

2 = 8O

USINT

1

Get /
Set

47

10

Timeout (milliseconds) (10ms

– 60000ms)

UINT

500

Get /
Set

47

100

Number of Valid Reads

(since power up)

UDINT

0

Get

101

Number of Read Errors

(since power up)

UDINT

0

Get

102

Number of Read Timeouts

(since power up)

UDINT

0

Get

110

Number of Valid Write

(since power up)

UDINT

0

Get

47

Stored to NVRAM