GE Industrial Solutions ASTAT BP User Manual
Page 110
ASTAT BP User Manual
110
GE Industrial Solutions
©2013 GE Company All Rights Reserved
C.8.2.
Instance Attributes (Instance 1)
Attribute
ID
Name
DeviceNet
Data Type
Data
Value
Access
Rule
Modbus Register
3
Run1 (Forward)
BOOL
0
Get / Set Bit 2: 40752
Bit 8-15: 0x5A
4
Run2 (Reverse)
BOOL
0
Get / Set Always 0
7
Running1
(Forward)
BOOL
0
Get
Bit 11: 40257
9
Ready
BOOL
0
Get
Bit 5: 40257
10
Faulted
BOOL
0
Get
Bit 15: 40257
11
Warning
BOOL
0
Get
Bit 6: 40257
15
Ctrl From Net
BOOL
1
Get
Always 1
100
Control Word
UINT
0
Get / Set 40752
(Read always 0-
since register is
not readable)
C.8.3.
Common Services
Service
Code
Implemented for
Service Name
Class Level
Instance Level
05
HEX
No
Yes
Reset
0E
HEX
Yes
Yes
Get Attribute Single
10
HEX
No
Yes
Set Attribute Single
C.9.
Modbus / Serial Object (65
HEX
– 1 Instance)
C.9.1.
Class Attributes (Instance 0)
Attribute
ID
Name
DeviceNet
Data Type
Data Value
Access
Rule
1
Revision
UINT
1
Get
C.9.2.
Instance Attributes (Instance 1)
Attribute
ID
Name
DeviceNet
Data Type
Data Value
Access
Rule
1
Modbus Slave ID (1-247)
USINT
1
Get /
Set
47
2
Baud Rate
0 = 4800
1 = 9600
2 = 19200
USINT
2
Get /
Set
47
3
Parity
0 = 8N
1 = 8E
2 = 8O
USINT
1
Get /
Set
47
10
Timeout (milliseconds) (10ms
– 60000ms)
UINT
500
Get /
Set
47
100
Number of Valid Reads
(since power up)
UDINT
0
Get
101
Number of Read Errors
(since power up)
UDINT
0
Get
102
Number of Read Timeouts
(since power up)
UDINT
0
Get
110
Number of Valid Write
(since power up)
UDINT
0
Get
47
Stored to NVRAM