GE Industrial Solutions ASTAT BP User Manual
Page 35
ASTAT BP User Manual
35
GE Industrial Solutions
©2013 GE Company All Rights Reserved
4.7.5
DUAL Settings Parameters
26
– Page 4
When
D.Set: Generator Parameters is required, do the following:
Program
PROG. Input C1 to GEN START/STOP. Refer to section 4.7.8 on page 39.
Connect control inputs voltage to aux. input terminal C1.
The following display appears:
D.Set: Generator
Parameters
Function &
Default
Range
Unit
Description
Starting VOLT-2
30%
10-50%
After
reaching
50% the
display
changes to:
Starting
CURR-2
100-400%.
27
% of mains
voltage
Sets the motor’s Starting Voltage in DUAL Setting
mode. (Motor’s torque is directly proportional to the
square of the voltage)
Refer to section 4.7.3 on page 28 parameter:
Starting Voltage
Starting CURR-2
100%
Current Limit-2
350% of Im
100-700%.
% of Motor
Current
Sets the motor’s highest current during starting in
DUAL Setting mode.
Refer to section 4.7.3 on page 28 parameter:
Current Limit.
Ramp UP-2
10 SEC.
1-30
28
sec.
Sets Ramp UP-2 time of the motor in DUAL Setting
mode.
Refer to section 4.7.3 on page 28 parameter:
Ramp UP Time.
Ramp DOWN-2
0 SEC.
1–30
29
sec.
Sets Ramp DOWN-2 time of the motor in DUAL Setting
mode.
Refer to section 4.7.4 on page 33 parameter:
Ramp DOWN time.
Motor Current-2
31 Amp.
50-100% of
STARTER
Current.
A.
Sets the motor’s Full load Ampere, Im, in DUAL Setting
mode.
Refer to section 4.7.2 on page 24 parameter:
Motor
Current.
Note:
Motor Current-2 can be set to an equal
or lower value than Motor Current set
in Main Settings page.
Store Settings
DUAL Settings
Same as
Store Settings Main Settings on
page 28.
26
Displays in MAXIMIZED MODE only. To change to this mode refer to parameter DISPLAY MODE on section 4.7.2 page 26.
27
The range of the Starting Volt-2 can be extended to 10-80% by using the EXPANDED SETTING as described in section 4.7.6 page 36.
28
The range of the Ramp UP-2 time can be extended to 1-90 sec. by using the EXPANDED SETTING as described in section 4.7.6 page 36.
29
The range of the Ramp DOWN-2 time can be extended to 1-90 sec. by using the EXPANDED SETTING as described in section 4.7.6 page 36.