Kickstart Time

0 Sec.

0 –1.0

sec.

Sets ASTAT-BP’s Kickstart Time.

21

Kickstart level is 80% Un.

Intended to start high friction loads that require high starting

torque for a short time.

A pulse of 80% Un without Current Limit is initiated to break the

load free.

Kickstart Time is adjustable, 0.1–1sec. After this pulse the

voltage is ramped down to

Starting Voltage setting

before ramping up again to full voltage according to the

Start

Settings.

Starting Voltage

30 %

Starting Current

100 %

10-50%

After

reaching

50% the

display

changes to:

Starting

Current

100-400%

22

% of

mains

voltage

Sets the motor’s Starting Voltage.

The motor’s torque is directly proportional to the square

of the voltage.

This adjustment also determines the inrush current and

mechanical shock. A setting that is too high may cause high

initial mechanical shock and high inrush current. This can occur

even if

Current Limit is set low because the Starting

Voltage setting overrides the Current Limit setting.

A setting that is too low may result in prolonged time until the

motor starts to turn. In general, this setting should ensure that

the motor starts turning immediately after start signal.

Note:
When

Starting Voltage is set its maximum value, this

displays changes to

Starting Current.

When

Starting Current is set the ASTAT-BP causes

current ramp instead of voltage ramp.

21

There is no Kickstart function when ASTAT-BP is connected in DELTA Conf.

22

The range of the Starting Voltage can be extended to 5-80% by using the EXPANDED SETTING as described in section 4.7.6 page 36.