Function &

Default

Range

Unit

Description

TIME OUT

OFF

0.1-

60/OFF

sec.

Sets MODBUS

TIME OUT. If no valid Modbus communication

during MODBUS

TIME OUT, the ASTAT-BP will trip.

Trip occurs only if the following conditions exist:

• S. Link Control is set to Enabled

• Station Number. is not set to OFF

If MODBUS

TIME OUT is set to OFF protection is disabled.

Store Settings

COMM. Parameters

Same as

Store Settings Main Settings on page 28.

Note:

After changing communication parameters and storing them,

control power must be switched OFF and ON to load the new

communication parameters.

4.7.11

Comm. Parameters

35

– Page 8 – With the Profibus optional PCB

Function &

Default

Range

Unit

Description

COMM. PROTOCOL

Profibus

Profibus/

Modbus/

DeviceNet

Sets ASTAT-BP’s communication protocol.

Operational when the optional communication PCB is

installed.

Baud Rate

AUTO (Profibus)

User can not change the

Baud Rate value.

Max. rate is 12 mega bit per second (MBPS).

Parity Check

AUTO (Profibus)

User can not change the

Parity Check value.

PROFIBUS Network ID

OFF

OFF, 1-126

Sets the Profibus network ID.

When set to OFF the Profibus card will not function.

S. Link Par. Set

Disabled

Enabled/

Disabled

Enables parameter modification via serial

communication

Ser. Link Control

Disabled

Enabled/

Disabled

Enables start, stop, reset, etc. via serial communication

TIME OUT

Auto (Profibus)

Auto

Do not change this parameter! Must be set to Auto

Store Settings

COMM. Parameters

Enabled/

Disabled

Same as

Store Settings Main Settings on

page 28.
Note:

After changing communication parameters and storing

them, control power must be switched OFF and ON to

load new communication parameters.

4.7.12

Comm. Parameters

35

– Page 8 – With the DeviceNet Optional PCB

Function &

Default

Range

Unit

Description

COMM. PROTOCOL

DeviceNet

Profibus/

Modbus/

DeviceNet

Sets ASTAT-BP’s communication protocol.

Operational when the optional communication PCB is

installed.

Baud Rate

Set Manually

Set the

Baud Rate by changing the position of the

rotary switches on the optional PCB as shown on section

C.1.5 page 103.