33..66
Operating Modes
Operating Mode
Key
Description
Starting Voltage
1
5 to 80% Un. Adjustable via
Starting Voltage parameter.
Kick Start
2
Fixed level of 80% Un with an adjustable time, 0-1 sec., via
Kickstart
Time parameter.
Acceleration Ramp
3
1-30 sec. (1-90
5
sec.). Adjustable via
Ramp UP Time.
Secondary ramp 1-30sec. (1-90
5
sec.). Adjustable via
Ramp UP-2
parameter.
Ramp up modes available are:
Soft Start Curve 0 (Standard)
Soft Start Curve 1!!-3!!
Soft Start Curve 4(Torque) for linear torque control
4
Fast ramp (if the motor is up to speed before the end of normal ramp time)
Running mode
5
Nominal voltage
Soft stop mode
6
Deceleration ramp 1-30sec. (1-90
5
sec.). Adjustable via
Ramp DOWN Time.
Secondary ramp 1-30sec. (1-90
5
sec.). Adjustable via
Ramp DOWN-2
parameter
.
Ramp down modes available are:
Soft Stop Curve 0 (Standard)
Soft Stop Curve 1!!-3!!
Soft Stop Curve 4(Torque) for linear torque control
7
Current limiting set point (100-500%xMotor Current)
8
Acceleration ramp (continuation after motor amps drop below the current
limit).
9
Standard stopping (coast to rest)
Starting by voltage ramp:
5
Refer to section 4.7.6 page 36 for expanded setting.