APPENDIX A -

MODBUS RTU PROTOCOL

A.1.

Introduction

This document summarizes the serial link protocol to / from the DIGITAL SOFT STARTER(ASTAT-BP).

Features:

RS485 Hardware.

Asynchronous serial link.

Half duplex.

Format: Modbus RTU Mode (Remote Terminal Unit Mode).

o Binary

o Each character contains 11 bits:

- One start bit

-8 data bits, least significant bit sent first.

- 1 Parity bit. Even / Odd / No can be selected.

- 1 Stop bit if Parity is used, 2 stop bits if Parity is not used.

o Cyclical Redundancy Check (CRC), 16 bits.

Baud Rates: 1200 / 2400 / 4800 / 9600 bits per second.

Response time of the ASTAT-BP:

o Normally, 4ms <= time response <= 40mS.

o For a long response, time response <= 200mS.

It is not recommended to transmit to the ASTAT-BP at a rate higher than once per second because this can

slow down ASTAT-BP response times.

After storing parameter settings, there is a 1 sec. time period during which transmission to the same ASTAT-

BP is forbidden.

Broadcast commands: not supported.

Notes:

*

It is recommended that you connect 120 OHM resistors to both ends of the serial link.

*

You must turn OFF (and ON again) power to the controller after changing Baud_Rate, Parity_Check or

Serial_Link_No (Slave Address). These parameters can only be modified manually and not through the

Serial Link.


WARNING

You must connect earth to the ASTAT-BP earth screw before connecting serial link wires.

Ignoring this instruction may result in permanent damage to the Serial Link Hardware

and might result in death or serious injury.