GE Industrial Solutions ASTAT BP User Manual
Page 38
ASTAT BP User Manual
38
GE Industrial Solutions
©2013 GE Company All Rights Reserved
Function &
Default
Range
Unit
Description
Auto Reset
Disabled
Enabled/
Disabled
Sets ASTAT-BP’s Auto Reset mode of operation.
The ASTAT-BP can be automatically reset for
Undervoltage and Phase Loss faults.
Refer to section 4.7.2 on page 26 for details on setting
Undervoltage protection.
To start the motor after
Undervoltage and Phase
Loss faults have been cleared, remove the START signal
and recommence the signal.
Auto Reset function has a non-programmable time delay
of 60 seconds.
Note:
The
Auto Reset operation is limited to 10 operations.
Thermistor Type
PTC
PTC/NTC
Sets input Thermistor Type
Measures the motor’s thermistor resistance and trips the
ASTAT-BP when the level decreases below set level.
Thermistor Trip
Disabled
Disabled,
0.1–10Kohm
Sets ASTAT-BP’s Thermistor Trip mode of operation.
Note:
Thermistor Trip has a factory preset time delay of 2 sec.
Undercurrent RST
Disabled
10–120min.,
Disabled.
Sets ASTAT-BP’s Undercurrent Reset time delay.
If the
Undercurrent RST setting is OFF then ASTAT-
BP will not automatically reset after an
Undercurrent
Trip fault occurs.
If you set the
Undercurrent RST setting to a time
value then ASTAT-BP will automatically reset with a
delay (the time defined for
Undercurrent RST). If the
start command is not removed, the motor will restart
automatically after the delay time.
During the delay time a message
U/C Fault Retry
In: XX Min. is displayed.
Refer to section 4.7.2 on page 26 for details on setting of
Undercurrent Trip.
Store Settings
Fault Settings
Same as
Store Settings Main Settings on
page 28.