GE Industrial Solutions ASTAT BP User Manual

Page 38

Advertising
background image

ASTAT BP User Manual

38

GE Industrial Solutions

©2013 GE Company All Rights Reserved

Function &

Default

Range

Unit

Description

Auto Reset

Disabled

Enabled/

Disabled

Sets ASTAT-BP’s Auto Reset mode of operation.

The ASTAT-BP can be automatically reset for

Undervoltage and Phase Loss faults.

Refer to section 4.7.2 on page 26 for details on setting

Undervoltage protection.

To start the motor after

Undervoltage and Phase

Loss faults have been cleared, remove the START signal

and recommence the signal.

Auto Reset function has a non-programmable time delay

of 60 seconds.
Note:

The

Auto Reset operation is limited to 10 operations.

Thermistor Type

PTC

PTC/NTC

Sets input Thermistor Type

Measures the motor’s thermistor resistance and trips the

ASTAT-BP when the level decreases below set level.

Thermistor Trip

Disabled

Disabled,

0.1–10Kohm

Sets ASTAT-BP’s Thermistor Trip mode of operation.
Note:

Thermistor Trip has a factory preset time delay of 2 sec.

Undercurrent RST

Disabled

10–120min.,

Disabled.

Sets ASTAT-BP’s Undercurrent Reset time delay.

If the

Undercurrent RST setting is OFF then ASTAT-

BP will not automatically reset after an

Undercurrent

Trip fault occurs.

If you set the

Undercurrent RST setting to a time

value then ASTAT-BP will automatically reset with a

delay (the time defined for

Undercurrent RST). If the

start command is not removed, the motor will restart

automatically after the delay time.

During the delay time a message

U/C Fault Retry

In: XX Min. is displayed.

Refer to section 4.7.2 on page 26 for details on setting of

Undercurrent Trip.

Store Settings

Fault Settings

Same as

Store Settings Main Settings on

page 28.