Current Limit

350% of Im

100-700%

% of

Motor

Current

Sets the motor’s highest current during starting.

A setting that is too high will increase the current drawn from

mains and speed up acceleration.

A setting that is too low may prevent the motor from completing

the acceleration process and reaching full speed. In general, this

setting should be set to a value that is high enough to prevent

stalling.

Current Limit is limited to the value of:

<350x(

Starter Current/Motor Current)>

with a minimum setting of 300% and a maximum

setting of 700%.

Note:

Current Limit does not operate during RUN and SOFT

STOP.

Ramp UP Time

10 SEC.

1-30

23

sec.

Sets Ramp UP Time of the motor.

Determines the motor’s voltage

Ramp UP Time, from initial to

full voltage.

It is recommended to set the

Ramp UP Time to the minimum

acceptable value (approx. 5 sec).

Notes:

Since

Current Limit overrides Ramp UP Time, when

Current Limit is set low, the starting time will be longer

than the

Ramp UP Time setting.

When the motor reaches full speed before voltage reaches

nominal,

Ramp UP Time setting is overridden, causing voltage

to quickly ramp-up to nominal.

Using

Soft Start Curve 1, 2, 3 prevents quick

ramp up.

23

The range of the Ramp UP Time can be extended to 1-90 sec. by using the EXPANDED SETTING as described in section 4.7.6 page 36.