C.4.3.
Common Services
Service Code
Implemented for
Service Name
Class Level
Instance Level
0E
HEX
Yes
Yes
Get_Attribute_Single
10
HEX
No
Yes
Set_Attribute_Single
C.5.
Assembly Object (04
HEX
– 4 Instances)
C.5.1.
Class Attributes (Instance 0)
Attribute ID
Name
DeviceNet
Data Type
Data
Value
Access Rule
1
Revision
UINT
2
Get
2
Max Instance
UINT
112
Get
100
Input Index
60 = Instance 60
61 = Instance 61
100 = Instance 100
USINT
2
Get / Set
42
101
Input Size (in bytes)
UINT
1
Get
102
Output Index
112 = Instance 112
USINT
0
Get / Set
43
103
Output Size (in bytes)
UINT
1
Get
C.5.2.
Output (O2T) Instance Attributes – Register 40752
Attribute ID Name
DeviceNet
Data Type
Data
Value
Access Rule
3
Output Data
USINT[]
0
Get/Set
C.5.2.1.
Output Instance 112 (0x70) – Control Output
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Reset
Slow Speed
Reverse
Slow Speed
Dual Adjust
Energy Save
Start
Soft Stop
Stop
C.5.3.
Input (T20) Instance Attributes – Register 40257
Attribute ID Name
DeviceNet
Data Type
Data
Value
Access Rule
3
Input Data
USINT[]
0
Get
C.5.3.1.
Input Instance 60 (0x3C) – Basic Softstart Input
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
At Reference
Reserved
Reserved
Reserved
Reserved
Running1
Reserved
Faulted / Trip
C.5.3.2.
Input Instance 61 (0x3D) – Extended Softstart Input
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
At
Reference
Reserved
Control
From Net
Ready
Running2
Running1 Warning Faulted / Trip
42
Stored to NVRAM
43
Stored to NVRAM