GE Industrial Solutions ASTAT BP User Manual

Page 106

Advertising
background image

ASTAT BP User Manual

106

GE Industrial Solutions

©2013 GE Company All Rights Reserved

C.4.3.

Common Services

Service Code

Implemented for

Service Name

Class Level

Instance Level

0E

HEX

Yes

Yes

Get_Attribute_Single

10

HEX

No

Yes

Set_Attribute_Single

C.5.

Assembly Object (04

HEX

– 4 Instances)

C.5.1.

Class Attributes (Instance 0)

Attribute ID

Name

DeviceNet

Data Type

Data

Value

Access Rule

1

Revision

UINT

2

Get

2

Max Instance

UINT

112

Get

100

Input Index

60 = Instance 60

61 = Instance 61

100 = Instance 100

USINT

2

Get / Set

42

101

Input Size (in bytes)

UINT

1

Get

102

Output Index

112 = Instance 112

USINT

0

Get / Set

43

103

Output Size (in bytes)

UINT

1

Get

C.5.2.

Output (O2T) Instance Attributes – Register 40752

Attribute ID Name

DeviceNet

Data Type

Data

Value

Access Rule

3

Output Data

USINT[]

0

Get/Set

C.5.2.1.

Output Instance 112 (0x70) – Control Output

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Reset

Slow Speed

Reverse

Slow Speed

Dual Adjust

Energy Save

Start

Soft Stop

Stop

C.5.3.

Input (T20) Instance Attributes – Register 40257

Attribute ID Name

DeviceNet

Data Type

Data

Value

Access Rule

3

Input Data

USINT[]

0

Get

C.5.3.1.

Input Instance 60 (0x3C) – Basic Softstart Input

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

At Reference

Reserved

Reserved

Reserved

Reserved

Running1

Reserved

Faulted / Trip

C.5.3.2.

Input Instance 61 (0x3D) – Extended Softstart Input

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

At

Reference

Reserved

Control

From Net

Ready

Running2

Running1 Warning Faulted / Trip

42

Stored to NVRAM

43

Stored to NVRAM