GE Industrial Solutions ASTAT BP User Manual
Page 98
ASTAT BP User Manual
98
GE Industrial Solutions
©2013 GE Company All Rights Reserved
B.4.
Actual Data Register Numbers (decimal)
Number
Parameter Name
Description
1
Logic Status
Logic status of ASTAT-BP. 1 indicates:
d15:
ASTAT-BP Tripped.
d14:
Motor Stopped.
d13:
Motor in Soft Stop Process.
d12:
Motor in Start Process.
d11:
Motor is Running.
d10:
Dual_Adjust On.
d9:
Motor is running with Energy Save On.
d8:
Motor is running at Slow Speed forward.
d7:
Motor is running at Slow Speed reverse.
d6:
Reserved
d5..d0: Reserved
2
Motor Current
Current, % FLA
3
Line Voltage
Line voltage, Volts
4
Phase Sequence
1: Correct phase seq. 0: Wrong phase seq.
5
Hardwired inputs
Discrete Hardwired control inputs:
d15..d8: Reserved.
d7:
External fault.
d6:
Reserved.
d5:
Reserved.
d4:
D.Adj / S.Spd / Rst (Programmable) Input.
d3:
E.Save / Rvrs / Rst (Programmable) Input.
d2:
Start Input.
d1:
Soft Stop Input.
d0:
Stop Input.
6
DIP switch
d15..d8: Reserved.
d7:
Prevent Setting Lock - (right-most)
d6:
Enlarged Setting Ranges
d5:
Language Selection.
d4:
Language Selection.
d3:
Reserved - Must be set to Off.
d2:
Generator Starting - Set to Off.
d1:
Reserved.
d0:
Min (OFF) / Max display pages- (left most)
10
Frequency
Main frequency, Hz
11
Thermistor Resistance
Thermistor resistance, tenth Kohm.
17
Logic status at power fail
Logic status at control power supply turns OFF.
18
Elapsed Run Time
Total Hours of motor runs.
19
Number of Starts
Total number of starts
20
Last start period
Duration of last start, Seconds
21
Last start peak I
Peak current during last starting process
22
Time to start
After too many starts trip, Seconds
23
Total trips
Total number of trips
24
Last Fault number
# of the fault that caused trip.
#
Fault
01:
Over Temperature
02:
Short Circuit Current
03:
Overload
04:
Under Current
05:
Under Voltage
06:
Over Voltage
07:
Phase Loss
08:
Phase Sequence
09:
Shorted SCR.
10:
Long Start Time
11:
Slow Speed Time
12:
Reserved
13:
External Fault
14:
Wrong Parameters