B.4.

Actual Data Register Numbers (decimal)

Number

Parameter Name

Description

1

Logic Status

Logic status of ASTAT-BP. 1 indicates:

d15:

ASTAT-BP Tripped.

d14:

Motor Stopped.

d13:

Motor in Soft Stop Process.

d12:

Motor in Start Process.

d11:

Motor is Running.

d10:

Dual_Adjust On.

d9:

Motor is running with Energy Save On.

d8:

Motor is running at Slow Speed forward.

d7:

Motor is running at Slow Speed reverse.

d6:

Reserved

d5..d0: Reserved

2

Motor Current

Current, % FLA

3

Line Voltage

Line voltage, Volts

4

Phase Sequence

1: Correct phase seq. 0: Wrong phase seq.

5

Hardwired inputs

Discrete Hardwired control inputs:

d15..d8: Reserved.

d7:

External fault.

d6:

Reserved.

d5:

Reserved.

d4:

D.Adj / S.Spd / Rst (Programmable) Input.

d3:

E.Save / Rvrs / Rst (Programmable) Input.

d2:

Start Input.

d1:

Soft Stop Input.

d0:

Stop Input.

6

DIP switch

d15..d8: Reserved.

d7:

Prevent Setting Lock - (right-most)

d6:

Enlarged Setting Ranges

d5:

Language Selection.

d4:

Language Selection.

d3:

Reserved - Must be set to Off.

d2:

Generator Starting - Set to Off.

d1:

Reserved.

d0:

Min (OFF) / Max display pages- (left most)

10

Frequency

Main frequency, Hz

11

Thermistor Resistance

Thermistor resistance, tenth Kohm.

17

Logic status at power fail

Logic status at control power supply turns OFF.

18

Elapsed Run Time

Total Hours of motor runs.

19

Number of Starts

Total number of starts

20

Last start period

Duration of last start, Seconds

21

Last start peak I

Peak current during last starting process

22

Time to start

After too many starts trip, Seconds

23

Total trips

Total number of trips

24

Last Fault number

# of the fault that caused trip.

#

Fault

01:

Over Temperature

02:

Short Circuit Current

03:

Overload

04:

Under Current

05:

Under Voltage

06:

Over Voltage

07:

Phase Loss

08:

Phase Sequence

09:

Shorted SCR.

10:

Long Start Time

11:

Slow Speed Time

12:

Reserved

13:

External Fault

14:

Wrong Parameters