4.7.4

Stop Settings

24

– Page 3

Function &

Default

Range

Uni

t

Description

Soft Stop Curve

0(Standard)

0 (Standard)

1 !!

2 !!

3 !!

4 (Torque)

Sets ASTAT-BP’s Soft Stop Curve.

Refer to section 4.7.4.1 on page 33.

Ramp DOWN Time

0 SEC.

1–30

25

Sec.

Sets Ramp DOWN Time of the motor.

Used for controlled deceleration of high friction loads.

Determines the motor’s voltage ramp down time.

End Torque

0 (MIN.)

0 (MIN.) – 10 (MAX.)

Sets End Torque during soft stop.

Determines torque towards the end of a soft stop.

If the current still flows after speed is softly reduced to

zero, you should increase the

End Torque setting.

Store Settings

Stop Settings

Same as

Store Settings Main Settings on

page 28.

44..77..44..11

Soft Stop Parameters

The ASTAT-BP incorporates 5 stopping curves that enable you to select the suitable torque curve

Soft Stop Curve 0 – Standard Curve (Default) – voltage is linearly reduced from nominal to zero.

The most stable and suitable curve for preventing prolonged stopping and motor overheating.

Soft Stop Curves 1, 2, 3 Pump Control – In some pump applications, when pumping to higher

elevation a considerable part of the torque is constant and does not decrease with speed.

24

Displays in MINIMIZED MODE and MAXIMIZED MODE.

25

The range of the Ramp DOWN Time can be extended to 1-90 sec. by using the EXPANDED SETTING as described in section 4.7.6 page 36.