Configure safety connections – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 102

Advertising
background image

102

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Chapter 5

Configure the Module in a GuardLogix Controller System

Configure Safety
Connections

Follow these steps to configure the module’s safety input connection.

1. From the Module Properties dialog box, click the Safety tab.

2. Click Advanced to open the Advanced Connection Reaction Time Limit

Configuration dialog box.

a. In the Requested Packet Interval (RPI) field, enter the input

connection RPI to support your application (between 6 and 500 ms).

The smallest input RPI allowed is 6 ms. Selecting small RPIs consumes
network bandwidth and may cause nuisance trips because other devices
cannot get access to the network.

As an example, a safety input module with only E-stop switches
connected may generally work well with settings of 50…100 ms. An
input module with a light curtain guarding a hazard may need the
fastest response possible. Selecting appropriate RPIs results in a system
with maximum (best) performance.