Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 107

Advertising
background image

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

107

Configure the Module for a SmartGuard Controller

Chapter 6

2. Click Browse.

3. Check ‘I want to input the address for the device on the selected network’.

4. Browse to the DeviceNet network, being sure to not click OK when the

browse is complete.

If you are unable to browse the DeviceNet network and see the POINT
Guard modules, the modules may have been previously configured to an
incompatible data rate or node address. Attempt to add these modules on
an isolated network to determine the node address and data rate.

5. Enter the current address for the device.

An out-of-box device uses address 63.

6. Click OK

7. Enter the new address for the device.

8. Click Apply.

9. Look for confirmation in the messages section.

3

4

5

6

7

8

9

Advertising