Precautions, European hazardous location approval – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 52

Advertising
background image

52

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Chapter 4

Install the Module

Precautions

Follow these precautions for use.

European Hazardous Location Approval

This equipment is intended for use in potentially explosive atmospheres as
defined by European Union Directive 94/9/EC and has been found to comply
with the Essential Health and Safety Requirements relating to the design and
construction of Category 3 equipment intended for use in Zone 2 potentially
explosive atmospheres, given in Annex II to this Directive.

Compliance with the Essential Health and Safety Requirements is assured by
compliance with EN 60079-15 and EN 60079-0.

WARNING:

This equipment must be used within its specified ratings as defined by

Rockwell Automation.

This equipment must be mounted in an ATEX-certified enclosure with a

minimum ingress protection rating of at least IP54 ( as defined in IEC 60529)
and used in an environment of not more than Pollution Degree 2 (as defined in
IEC 60664-1) when applied in Zone 2 environments. The enclosure must have a
tool-removable cover or door.

Provision shall be made to prevent the rated voltage from being exceeded by

transient disturbances of more than 140% of the rated voltage when applied in
Zone 2 environments.

This device must be used only with ATEX-certified Rockwell Automation

terminal bases.

Do not disconnect equipment unless power has been removed or the area is

known to be nonhazardous.