Safety input fault recovery, Input delays, Safety input fault recovery input delays – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 30

Advertising
background image

30

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Chapter 2

Safety Inputs, Safety Outputs, and Safety Data

Safety Input Fault Recovery

If an error is detected, the safety input data remains in the OFF state. Follow this
procedure to activate the safety input data again.

1. Remove the cause of the error.

2. Place the safety input (or safety inputs) into the safe state.

3. Allow the input-error latch time to elapse.

After these steps are completed, the I/O indicator (red) turns off.
The input data is now active.

Input Delays

On-delay—An input signal is treated as Logic 0 during the on-delay time
(0…126 ms, in increments of 6 ms) after the input contact’s rising edge. The
input turns on only if the input contact remains on after the on-delay time has
elapsed. This helps prevent rapid changes of the input data due to
contact bounce.

Figure 10 - On-delay

Off-delay—An input signal is treated as Logic 1 during the off-delay time
(0…126 ms, in increments of 6 ms) after the input contact’s falling edge.
The input turns off only if the input contact remains off after the off delay time
has elapsed. This helps prevent rapid changes of the input data due to contact
bounce.

Figure 11 - Off-delay

44094

On-delay

ON
OFF

ON
OFF

Input Signal

Safety Input
Network Data

44095

Safety Input
Network Data

Off-delay

Input Signal

ON
OFF

ON
OFF

Advertising