Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

103

Configure the Module in a GuardLogix Controller System

Chapter 5

b. Use the default values for Timeout Multiplier (2) and Network Delay

Multiplier (200).

A connection status tag exists for every connection.

If the RPI and connection reaction time limit for the network are set
appropriately, then this status tag should always remain low. Monitor all
connection status bits to verify that they are not going high
intermittently due to timeouts.

For more information about the Advanced Connection Reaction Time
Limit Configuration dialog box, refer to the GuardLogix Controllers
User Manual, publication

1756-UM020

, the GuardLogix 5570

Controllers User Manual, publication

1756-UM022

, or Compact

GuardLogix Controllers User Manual, publication

1768-UM002

.

Configuration Ownership

The connection between the owner and the POINT Guard I/O module is based
on the following:

POINT Guard I/O module number
POINT Guard I/O safety network number
GuardLogix slot number
GuardLogix safety network number
Path from the GuardLogix controller to the POINT Guard I/O module
Configuration signature

If any differences are detected, the connection between the GuardLogix
controller and the POINT Guard I/O module is lost, and the yellow yield icon
appears in the controller project tree. For more information, see

Chapter 8

.

IMPORTANT

Analyze each safety channel to determine what is appropriate. The default
Timeout Multiplier of 2 and Network Delay Multiplier of 200 creates a
worst-case input connection-reaction time limit of 4 times the RPI, and an
output connection-reaction time limit of 3 times the RPI. Changes to these
parameters should be approved only after a thorough review by a safety
administrator.