88

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Chapter 5

Configure the Module in a GuardLogix Controller System

c. From the Electronic Keying pull-down menu, choose the appropriate

keying method from the following options.

d. From the Configured By pull-down menu, choose the method by

which this module is configured.

e. From the Input Data pull-down menu, choose None.

None is the only valid selection, as this is an output-only safety module.

f. From the Output Data pull-down menu, choose from the following:

Choose

Description

Exact Match

All of the parameters must match or the inserted module rejects a
connection to the controller.

Compatible Module

Lets an I/O module determine whether it can emulate the module defined
in the configuration sent from the controller.

Choose

Description

This Controller

This selection directs the controller to configure and control the safety
outputs.
The Output Data selection will be set to Safety.

External Means

This selection directs the controller to establish a safety input connection
only, and the controller will not configure the module or be able to control
the safety outputs.
The Output Data selection will be set to None.

Choose

Description

Safety

Automatically selected when Configured By = This controller. Results in an output
connection. Selecting Safety creates output tags and enables these outputs for use in the
Safety Task.

None

Automatically selected when Configured By = External. Selecting None results in an
input only connection to the module. Status is read, but no outputs are written.