Get I/O Diagnostic Status from Modules in Logix Systems

Appendix B

Table 16 - Fault Code Definitions for 1734-IE4S Modules

Fault Code

Description

Definition

Recommended Action

2

Signal Over Range

Exceeded configured range

Check field wiring and/or power

3

Signal Under Range

Below configured range

Check field wiring and/or power

4

Signal Test Failure

Undefined error for IE4S

If the problem persists, replace module

5

Dual Channel Discrepancy

Exceeded tolerance between dual channels

Check field sensors to determine cause of discrepancy

6

Error in other Dual Channel
Input

Partner channel faulted

Troubleshoot partner channel fault

100

Sensor Supply Overcurrent

Exceeded specification

Check field wiring and sensor power draw

101

Sensor Undercurrent

Too little current drawn from sensor power

Check field wiring and sensor power draw

102

ADC CPU Timing Fault

ADC missed a clock, failed a sync, or watchdog
(combination flag)

If the problem persists, replace module

103

3.3V Undervoltage

3.3V supply voltage was detected too low

If the problem persists, replace module

104

3.3V Overvoltage

3.3V supply voltage was detected too high

If the problem persists, replace module

105

CPU Fault

ADC failed register, instruction, or flag diagnostic

If the problem persists, replace module

106

Flash Fault

FLASH test detected bit errors

If the problem persists, replace module

107

RAM fault

RAM test detected bit errors

If the problem persists, replace module

108

Single Channel
Discrepancy

Dual measurements of single channel disagree

If the problem persists, replace module

109

Tach Dual Low

Both channels LO at same time

Check sensor signal timing

110

Undefined Error

Undefined error

If the problem persists, replace module

111

Flash Enable Fault

ADC's nonvolatile memory drawing too much current
(micro jumped to nonvolatile for some reason)

If the problem persists, replace module

112

Serial Pattern Fault

Serial communication pattern errors detected

Check field wiring for proper grounding/shielding
Verify that the temperature within the enclosure is not excessive
If the problem persists, replace module

113

Channel Uniqueness Fault

Pulse testing of ADC multiplexor revealed improper
channel

If the problem persists, replace module

114

Watchdog Fault

ADC watchdog timed out

If the problem persists, replace module

115

Sync Timeout Fault

ADC conversion out of sync

If the problem persists, replace module

116

Missing Clock fault

ADC detected a missing clock

If the problem persists, replace module

117

SCI Tx fault

Serial communication bit errors detected

Check field wiring for proper grounding/shielding
Verify temperature within enclosure is not excessive
If the problem persists, replace module

118

ADC fault

ADC test pattern failure

If the problem persists, replace module

119

ADC neighbor 1.8V fault

ADC detected out-of-range voltage on its partner

If the problem persists, replace module

120

ADC channel config
mismatch

Dual ADCs are not configured the same

If the problem persists, replace module

121

SPI sequence number
mismatch

Serial communication state machines are out of sync

If the problem persists, replace module

122

Runtime 3.3V over/under
error

3.3V supply voltage was detected too high or too low

If the problem persists, replace module

125

Field I/O power is missing

24V power is not within specification

Check field power supply and wiring

126

Startup 3.3V over/under
error

OV-UV detector failed startup test

If the problem persists, replace module

127

Sensor power/input wiring
error

Sensor power to input signal violation detected

Check field wiring