Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 166

Advertising
background image

166

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Appendix C

Specifications

POINTBus

POINT Bus current, max

110 mA @ 5V

Power Dissipation, max

2.2 W

Thermal Dissipation, max

7.5 BTU/hr

Field Power Input

19.2…28.8V DC, 65 mA, Class 2

Sensor Output

Output type

Sensor power supply, 24V DC

Rated output current per point

150 mA max. per output @ 55°C (131 °F)

On-state voltage drop

≤ 0.5V

Leakage current, max

< 0.1 mA

Over current detection

Yes

Open load detection

Yes

Sensor Supply Undercurrent Fault

Detected at < 4.0 mA (2.5 mA typical)

Aggregate current of sensor outputs per
module

600 mA

Terminal base screw torque

See terminal base specifications

(1) For more information, see

Step Response and Filter Response for 1734-IE4S Modules on page 167

.

(2) Use this conductor category information for planning conductor routing. Refer to the Industrial Automation Wiring and Grounding

Guidelines, publication

1770-4.1

.

(3) For more information, see

Figure 58

,

Accuracy Drift vs Temperature (Current mode) on page 172

.

Attribute

1734-IE4S Series A