Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

121

Configure the Module for a SmartGuard Controller

Chapter 6

4. To add a safety connection, from the Connection Name pull-down menu,

choose one of these options.

The more status that is read, the larger the packet size.

5. From the Connection Type pull-down menu, for this example choose

Multicast.

6. From the Configuration pull-down menu, for this example choose

Configuration signature must match.

7. In the Requested Packet Interval (RPI) box, enter 10 ms.

8. In the Connection Reaction Time Limit (CRTL), enter 40.1 ms.

Choose

Description

1734

-IB8S

[IN] Safety

Control of safety inputs

[IN] Safety +
Combined Status

(1)

- Muting

Control of safety inputs
Status for one bit for all inputs
Muting status is available

[IN] Safety + Pt. Status

Control of safety inputs
Individual status for each input point

[IN] Safety + Pt. Status -
Muting

Control of safety inputs
Individual status for each input point
Muting status available

[IN] Safety + Pt. Status-
Muting - Test Output

Control of safety inputs
Individual status for each input point
Muting status available
Test output status available

[OUT] Test

Control of test outputs

173

4-

OB

8S

[IN] Safety Monitor -
Combined Status - Power

Monitor safety outputs
Status for one bit for all outputs
Power status available

[IN] Safety Output Status

Individual status for each output point

[IN] Safety Output Status+
Monitor

Individual status for each output point
Monitor safety outputs

[OUT] Safety

Control of safety outputs

17

34-I

E4S

(2

)

[IN] Channel and Combined
Alarm Status

Combined channel status and alarm status for each input point

[IN] Channel Status, Alarm
Status

Individual status for each input point
Combined alarm status for each input point
Power status

[OUT] Tach Reset

Resets a latched overfrequency condition and enables the module to
begin calculating frequency again.

(1) Most digital input connections use Combined Status.

(2) Other connection options are available via RSNetWorx for DeviceNet software, but their use with a SmartGuard controller

is not recommended.