Configure the safety digital outputs – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual

Page 90

Advertising
background image

90

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

Chapter 5

Configure the Module in a GuardLogix Controller System

6. Click OK again to apply your changes.

The I/O Configuration tree displays the 1734-OB8S module.

Configure the Safety Digital Outputs

Follow this procedure to configure the safety digital outputs.

1. From the Module Properties dialog box, click the Output Configuration

tab.

2. Assign the Point Operation Type.

3. Assign the Point Mode.

Choose

Description

Single

The output is treated as a single channel.

Dual (default)

The POINT Guard I/O module treats the outputs as a pair. It always sets them HI or LO as a
matched pair. Safety logic must set both of these outputs ON or OFF at the same time or
the module declares a channel fault.

Choose

Description

Not Used

The output is disabled.

Safety

The output point is enabled and does not perform a pulse test on the output.

Safety Pulse
Test

The output point is enabled and performs a pulse test on the output. When the output is
energized, the output pulses low briefly. The pulse test detects whether the output is
functioning properly.