Rockwell Automation Publication 1734-UM013J-EN-P - July 2014

109

Configure the Module for a SmartGuard Controller

Chapter 6

Set Up Your DeviceNet
Network

Before you begin to design a project with RSNetWorx for DeviceNet software,
follow these procedures.

1. From RSLinx software, open RSWho and select the SmartGuard driver.

RSWho browses the DeviceNet network connected to the SmartGuard
controller.

In this example, three POINT Guard I/O modules are connected to the
SmartGuard controller.

If RSLinx software finds the nodes on the DeviceNet network,
RSNetWorx for DeviceNet software also finds the nodes.

2. Open RSNetWorx for DeviceNet software.

3. From the Networks menu, choose Online.

4. Select the SmartGuard driver and click OK.